Point Name 

BACnet 

Object 

Type 

BACnet 

Object 

ID 

EIP Tag Name  EIP 

Class 

EIP 

Attribute 

EIP 

Address 

EIP 

Offset 

LonWorks Name 

LonWorks SNVT 

Type 

Engineers Key 086 

AI 

114  AI_XXX[136] 

X01 

136  nvoEngKey086_XXX 

SNVT_count_f 

Engineers Key 087 

AI 

115  AI_XXX[137] 

X01 

137  nvoEngKey087_XXX 

SNVT_count_f 

Engineers Key 088 

AI 

116  AI_XXX[138] 

X01 

138  nvoEngKey088_XXX 

SNVT_count_f 

Engineers Key 089 

AI 

117  AI_XXX[139] 

X01 

139  nvoEngKey089_XXX 

SNVT_count_f 

Engineers Key 090 

AI 

118  AI_XXX[140] 

X01 

140  nvoEngKey090_XXX 

SNVT_count_f 

Engineers Key 091 

AI 

119  AI_XXX[141] 

X01 

141  nvoEngKey091_XXX 

SNVT_count_f 

Engineers Key 092 

AI 

120  AI_XXX[142] 

X01 

142  nvoEngKey092_XXX 

SNVT_count_f 

Engineers Key 093 

AI 

121  AI_XXX[143] 

X01 

143  nvoEngKey093_XXX 

SNVT_count_f 

Engineers Key 094 

AI 

122  AI_XXX[144] 

X01 

144  nvoEngKey094_XXX 

SNVT_count_f 

Engineers Key 095 

AI 

123  AI_XXX[145] 

X01 

145  nvoEngKey095_XXX 

SNVT_count_f 

Engineers Key 096 

AI 

124  AI_XXX[146] 

X01 

146  nvoEngKey096_XXX 

SNVT_count_f 

Engineers Key 097 

AI 

125  AI_XXX[147] 

X01 

147  nvoEngKey097_XXX 

SNVT_count_f 

Engineers Key 098 

AI 

126  AI_XXX[148] 

X01 

148  nvoEngKey098_XXX 

SNVT_count_f 

Engineers Key 099 

AI 

127  AI_XXX[149] 

X01 

149  nvoEngKey099_XXX 

SNVT_count_f 

Engineers Key 100 

AI 

128  AI_XXX[150] 

X01 

150  nvoEngKey100_XXX 

SNVT_count_f 

Engineers Key 101 

AI 

129  AI_XXX[151] 

X01 

151  nvoEngKey101_XXX 

SNVT_count_f 

Engineers Key 102 

AI 

130  AI_XXX[152] 

X01 

152  nvoEngKey102_XXX 

SNVT_count_f 

Engineers Key 103 

AI 

131  AI_XXX[153] 

X01 

153  nvoEngKey103_XXX 

SNVT_count_f 

Engineers Key 104 

AI 

132  AI_XXX[154] 

X01 

154  nvoEngKey104_XXX 

SNVT_count_f 

Engineers Key 105 

AI 

133  AI_XXX[155] 

X01 

155  nvoEngKey105_XXX 

SNVT_count_f 

Engineers Key 106 

AI 

134  AI_XXX[156] 

X01 

156  nvoEngKey106_XXX 

SNVT_count_f 

Engineers Key 107 

AI 

135  AI_XXX[157] 

X01 

157  nvoEngKey107_XXX 

SNVT_count_f 

Engineers Key 108 

AI 

136  AI_XXX[158] 

X01 

158  nvoEngKey108_XXX 

SNVT_count_f 

Engineers Key 109 

AI 

137  AI_XXX[159] 

X01 

159  nvoEngKey109_XXX 

SNVT_count_f 

Engineers Key 110 

AI 

138  AI_XXX[160] 

X01 

160  nvoEngKey110_XXX 

SNVT_count_f 

Engineers Key 111 

AI 

139  AI_XXX[161] 

X01 

161  nvoEngKey111_XXX 

SNVT_count_f 

Engineers Key 112 

AI 

140  AI_XXX[162] 

X01 

162  nvoEngKey112_XXX 

SNVT_count_f 

Engineers Key 113 

AI 

141  AI_XXX[163] 

X01 

163  nvoEngKey113_XXX 

SNVT_count_f 

Engineers Key 114 

AI 

142  AI_XXX[164] 

X01 

164  nvoEngKey114_XXX 

SNVT_count_f 

Engineers Key 115 

AI 

143  AI_XXX[165] 

X01 

165  nvoEngKey115_XXX 

SNVT_count_f 

Engineers Key 116 

AI 

144  AI_XXX[166] 

X01 

166  nvoEngKey116_XXX 

SNVT_count_f 

Engineers Key 117 

AI 

145  AI_XXX[167] 

X01 

167  nvoEngKey117_XXX 

SNVT_count_f 

Engineers Key 118 

AI 

146  AI_XXX[168] 

X01 

168  nvoEngKey118_XXX 

SNVT_count_f 

Engineers Key 119 

AI 

147  AI_XXX[169] 

X01 

169  nvoEngKey119_XXX 

SNVT_count_f 

Engineers Key 120 

AI 

148  AI_XXX[170] 

X01 

170  nvoEngKey120_XXX 

SNVT_count_f 

Engineers Key 121 

AI 

149  AI_XXX[171] 

X01 

171  nvoEngKey121_XXX 

SNVT_count_f 

Engineers Key 122 

AI 

150  AI_XXX[172] 

X01 

172  nvoEngKey122_XXX 

SNVT_count_f 

Engineers Key 123 

AI 

151  AI_XXX[173] 

X01 

173  nvoEngKey123_XXX 

SNVT_count_f 

Engineers Key 124 

AI 

152  AI_XXX[174] 

X01 

174  nvoEngKey124_XXX 

SNVT_count_f 

Engineers Key 125 

AI 

153  AI_XXX[175] 

X01 

175  nvoEngKey125_XXX 

SNVT_count_f 

Engineers Key 126 

AI 

154  AI_XXX[176] 

X01 

176  nvoEngKey126_XXX 

SNVT_count_f 

Engineers Key 127 

AI 

155  AI_XXX[177] 

X01 

177  nvoEngKey127_XXX 

SNVT_count_f 

Engineers Key 128 

AI 

156  AI_XXX[178] 

X01 

178  nvoEngKey128_XXX 

SNVT_count_f 

Engineers Key 129 

AI 

157  AI_XXX[179] 

X01 

179  nvoEngKey129_XXX 

SNVT_count_f 

Engineers Key 130 

AI 

158  AI_XXX[180] 

X01 

180  nvoEngKey130_XXX 

SNVT_count_f 

Engineers Key 131 

AI 

159  AI_XXX[181] 

X01 

181  nvoEngKey131_XXX 

SNVT_count_f 

Engineers Key 132 

AI 

160  AI_XXX[182] 

X01 

182  nvoEngKey132_XXX 

SNVT_count_f 

Engineers Key 133 

AI 

161  AI_XXX[183] 

X01 

183  nvoEngKey133_XXX 

SNVT_count_f 

Engineers Key 134 

AI 

162  AI_XXX[184] 

X01 

184  nvoEngKey134_XXX 

SNVT_count_f 

Engineers Key 135 

AI 

163  AI_XXX[185] 

X01 

185  nvoEngKey135_XXX 

SNVT_count_f 

Engineers Key 136 

AI 

164  AI_XXX[186] 

X01 

186  nvoEngKey136_XXX 

SNVT_count_f 

Engineers Key 137 

AI 

165  AI_XXX[187] 

X01 

187  nvoEngKey137_XXX 

SNVT_count_f 

Engineers Key 138 

AI 

166  AI_XXX[188] 

X01 

188  nvoEngKey138_XXX 

SNVT_count_f 

Engineers Key 139 

AI 

167  AI_XXX[189] 

X01 

189  nvoEngKey139_XXX 

SNVT_count_f 

Engineers Key 140 

AI 

168  AI_XXX[190] 

X01 

190  nvoEngKey140_XXX 

SNVT_count_f 

Engineers Key 141 

AI 

169  AI_XXX[191] 

X01 

191  nvoEngKey141_XXX 

SNVT_count_f 

Engineers Key 142 

AI 

170  AI_XXX[192] 

X01 

192  nvoEngKey142_XXX 

SNVT_count_f 

Engineers Key 143 

AI 

171  AI_XXX[193] 

X01 

193  nvoEngKey143_XXX 

SNVT_count_f 

Engineers Key 144 

AI 

172  AI_XXX[194] 

X01 

194  nvoEngKey144_XXX 

SNVT_count_f 

Engineers Key 145 

AI 

173  AI_XXX[195] 

X01 

195  nvoEngKey145_XXX 

SNVT_count_f 

Engineers Key 146 

AI 

174  AI_XXX[196] 

X01 

196  nvoEngKey146_XXX 

SNVT_count_f 

Engineers Key 147 

AI 

175  AI_XXX[197] 

X01 

197  nvoEngKey147_XXX 

SNVT_count_f 

Engineers Key 148 

AI 

176  AI_XXX[198] 

X01 

198  nvoEngKey148_XXX 

SNVT_count_f 

Engineers Key 149 

AI 

177  AI_XXX[199] 

X01 

199  nvoEngKey149_XXX 

SNVT_count_f 

Summary of Contents for MB485ETH-CG

Page 1: ...building management system or PLC using the BACnet IP BACnet MS TP EtherNet IP or Modbus TCP IP protocols Multiple devices can be connected to a single communication gateway Configuration is done usin...

Page 2: ...note that the manufacturer MSA Safety dba Sierra Monitor does not provide direct support for this Fireye branded product Support Contact Information Fireye Inc 3 Manchester Road Derry NH 03038 Custome...

Page 3: ...H CG 3 pin power port Section 5 5 6 Connect a PC to the MB485ETH CG via Ethernet cable or by the MB485ETH CG s Wi Fi Access Point Section 6 7 Setup Web Server Security and login via web browser Sectio...

Page 4: ...17 6 1 1 1 Changing the Subnet of the Connected PC 17 6 1 1 2 Connecting to the MB485ETH CG Over Wi Fi Access Point 18 7 Setup Web Server Security 19 7 1 Login to the MB485ETH CG 19 7 2 Select the Sec...

Page 5: ...Appendix B 6 1 User Management 58 Appendix B 6 1 1 Create Users 59 Appendix B 6 2 Edit Users 60 Appendix B 6 2 1 Delete Users 61 Appendix B 6 3 Change MB485ETH CG Password 62 Appendix B 7 SMC Cloud Co...

Page 6: ...Wi Fi AP Network Settings 27 Figure 26 Generic Web App Page First Login 28 Figure 27 SMC Cloud Opt Out Warning Window 29 Figure 28 Welcome to SMC Cloud Email 30 Figure 29 Setting User Details 31 Figur...

Page 7: ...ate Loaded 57 Figure 58 FS GUI User Management 58 Figure 59 Create User Window 59 Figure 60 Setup Users 60 Figure 61 Edit User Window 60 Figure 62 Setup Users 61 Figure 63 User Delete Warning 61 Figur...

Page 8: ...s that a product has passed a series of rigorous tests conducted by an independent laboratory which verifies that the product correctly implements the BACnet features claimed in the listing The mark i...

Page 9: ...tested profiles configurations for the supported devices Connectivity Diagram The MB485ETH CG can connect with the SMC Cloud The SMC Cloud allows technicians the OEM s support team and MSA Safety s s...

Page 10: ...00 Modbus RTU ZB110_FSG Modbus RTU PPC6000_NX6100 Modbus RTU E110 Modbus RTU MicroM Modbus RTU BurnerPRO_Gen_3 Modbus RTU NXCESO2 Modbus RTU FX_Series_Servos Modbus RTU ACS550 Modbus RTU Insight_Insig...

Page 11: ...PA W44 units have the following 4 ports Ethernet Wi Fi RS 485 RS 485 RS 232 4 2 Point Count Capacity The total number of points presented to the device s attached to the MB485ETH CG cannot exceed Part...

Page 12: ...The Node ID assigned is used for deriving the Device Instance for BACnet IP and BACnet MS TP Section 10 5 NOTE The Modbus TCP IP field protocol Node IDs are automatically set to be the same value as...

Page 13: ...485 Serial Network Connect the RS 485 network wires to the 3 pin RS 485 connector on the R2 port Figure 7 o Use standard grounding principles for RS 485 GND See Section 6 for information on connecting...

Page 14: ...is in line with the BACnet spec It should only be enabled at one point on the bus for example on the field port were there are very weak bias resistors of 100k Since there are no jumpers many gateways...

Page 15: ...stor is also used to reduce noise It pulls the two lines of an idle bus together However the resistor would override the effect of any bias resistors if connected NOTE The R1 and R2 DIP Switches apply...

Page 16: ...commended Figure 10 Required Current Draw for the MB485ETH CG Apply power to the MB485ETH CG as shown below in Figure 11 Ensure that the power supply used complies with the specifications provided in...

Page 17: ...ferent IP networks assign a static IP Address to the PC on the 192 168 1 xxx network For Windows 10 Find the search field in the local computer s taskbar usually to the right of the windows icon and t...

Page 18: ...TH CG with Wi Fi To connect to the MB485ETH CG Wi Fi Access Point Click the icon found in the bottom right corner of the computer screen to open the available Wireless Network Connections Select the d...

Page 19: ...lbox utility See Appendix A 1 for instructions 7 1 Login to the MB485ETH CG The first time the MB485ETH CG GUI is opened in a browser the IP Address for the gateway will appear as untrusted This will...

Page 20: ...admin and the Password found on the label of the MB485ETH CG NOTE There is also a QR code in the top right corner of the MB485ETH CG label that shows the default unique password when scanned NOTE A us...

Page 21: ...t allows the user to select which mode the MB485ETH CG should use NOTE Cookies are used for authentication NOTE To change the web server security mode after initial setup go to Appendix B 5 The sectio...

Page 22: ...their respective fields If the Private Key is encrypted type in the associated Passphrase Click Save A Redirecting message will appear After a short time the Web Configurator page will open 7 2 2 HTTP...

Page 23: ...tab on the left side of the screen Click the Network tab that appears to open the Network Settings page A warning message will appear when performing the first time setup click the Exit Registration b...

Page 24: ...Settings The Common Settings make it possible to choose the primary connection when both Ethernet and Wi Fi Client connections are available NOTE The default Primary Connection is Ethernet Select the...

Page 25: ...Gateway and Domain Name Server1 2 NOTE If connected to a router set the Default Gateway to the same IP Address as the router Click Update IP Settings then click on System Restart to restart the Gatewa...

Page 26: ...le DHCP to automatically assign all Wi Fi Client network settings or manually modify the setting using the fields immediately below IP Address Network etc NOTE If connected to a router set the IP gate...

Page 27: ...cess Point SSID Access Point Password SSID Broadcast and Channel NOTE The default channel is 11 The default IP Address is 192 168 50 1 Click Update Wi Fi Settings then click on the System Restart to r...

Page 28: ...and hosts local applications for device configuration management as well as maintenance For more information about the SMC Cloud refer to the SMC Cloud Start up Guide 9 1 Choose Whether to Integrate S...

Page 29: ...that appears and click the Exit Registration button skip to Section 10 to continue MB485ETH CG configuration o To ignore SMC Cloud setup until the next time the MB485ETH CG Web App is opened click a...

Page 30: ...e manufacturer s support team and follow the instructions below to set up login details The Welcome to SMC Cloud email will appear as shown below NOTE If no SMC Cloud email was received check the spam...

Page 31: ...elds and click the checkbox to agree to the privacy policy and terms of service NOTE If access to data logs using RESTful API is needed do not include in the password Click Save to save the user detai...

Page 32: ...rver When first logging onto the MB485ETH CG the Web App will open on the SMC Cloud page NOTE If a warning message appears instead go to Appendix B 7 to resolve the connecton issue Click Get Started t...

Page 33: ...ls and SMC Cloud account credentials o Enter user details and click Next o Enter the site details by entering the physical address fields or the latitude and longitude then click Next Figure 31 SMC Cl...

Page 34: ...rrier o Enter Name and Description required then click Next o Enter user credentials and click Register Device Figure 33 SMC Cloud Registration Gateway Details Figure 34 SMC Cloud Registration SMC Clo...

Page 35: ...ick the Close button and the following screen will appear listing the device details and additional information auto populated by the MB485ETH CG NOTE Update these details at any time by going to the...

Page 36: ...istration credentials NOTE If the login password is lost see the SMC Cloud Start up Guide for recovery instructions On first login the Privacy Policy window will appear Read the Terms of Service click...

Page 37: ...2020 Carrier 37 NOTE For additional SMC Cloud instructions see the SMC Cloud Start up Guide Figure 38 SMC Cloud Landing Page...

Page 38: ...then click Configuration NOTE For information on the System Status button go to Appendix B 8 Then click the Profiles Configuration button to go to the Web Configurator page NOTE For Web App instructio...

Page 39: ...only visible when the associated protocol is selected NOTE If Modbus TCP IP was selected and is used for the field protocol skip Section 10 3 Device profiles are NOT used for Modbus TCP IP Ensure tha...

Page 40: ...re shown below the configuration parameters The Active Profiles section lists the currently active device profiles including previous Web Configurator additions This list is empty for new installation...

Page 41: ...ings on the device and correspond to the device IP Address and TCP_ID Section 4 3 3 Then press the Submit button to add the Profile to the list of devices to be configured Repeat this process until al...

Page 42: ...et Node_ID For example if the desired Device Instance for the device 1 is 50 001 and the following is true Device 1 has a Node ID of 1 Device 2 has a Node ID of 22 Device 3 has a Node ID of 33 Then pl...

Page 43: ...he steps outlined in Section 10 1 to access the MB485ETH CG Web Configurator At the bottom left of the page click the Clear Profiles and Restart button Once restart is complete all past profiles disco...

Page 44: ...and complete the installation Connect a standard Cat 5 Ethernet cable between the user s PC and MB485ETH CG Double click on the FS Toolbox Utility and click Discover Now on the splash page Check for...

Page 45: ...G into the web browser or use the MB485ETH CG Toolbox to connect to the MB485ETH CG Click on Diagnostics Button then click on view and then on connections If there are any errors showing on the Connec...

Page 46: ...e device was listed under the Web Configurator Active Profiles Section 10 3 No COMS on Modbus TCP IP side To fix check the following o Visual observations of LEDs on the MB485ETH CG Appendix A 4 o Che...

Page 47: ...nterface to support for evaluation PWR The power light should always show steady green when connected to a functioning power source RX The RX LED will flash when a message is received on the serial po...

Page 48: ...Diagnostics page via one of the following methods o Open the MB485ETH CG FS GUI page and click on Diagnostics in the Navigation panel o Open the MB485ETH CG Toolbox software and click the diagnose ic...

Page 49: ...Capture is complete email it to technical support The Diagnostic Capture will accelerate diagnosis of the problem Ensure that MB485ETH CG Toolbox is loaded onto the local PC Otherwise download the MB...

Page 50: ...e Start Diagnostic button o Wait for the capture period to finish and the Diagnostic Test Complete window will appear Step 2 Send Log o Once the diagnostic test is complete a zip file is saved on the...

Page 51: ...Instructions For instructions on how to reset a MB485ETH CG back to its factory released state see ENOTE MB485ETH CG Next Gen Recovery Appendix A 8 Internet Browser Software Support The following web...

Page 52: ...o the following a Click on Setup b Click on File Transfer c Click on the General tab 5 In the General tab click on Choose Files and select the web img file extracted in step 1 6 Click on the orange Su...

Page 53: ...2020 Carrier 53 Appendix B 3 Mounting The MB485ETH CG can be mounted using the DIN rail mounting bracket on the back of the unit Figure 53 DIN Rail Din Rail Bracket...

Page 54: ...54 2020 Carrier Appendix B 4 Physical Dimension Drawing Figure 54 MB485ETH CG FPA W44 Dimensions R1 Serial Port Power Port Wi Fi Antenna Socket R2 Serial Port...

Page 55: ...endix B 5 Change Web Server Security Settings After Initial Setup NOTE Any changes will require a MB485ETH CG reboot to take effect From the FS GUI page click Setup in the Navigation panel Figure 55 F...

Page 56: ...1 Change Security Mode Click Security in the Navigation panel Click the Mode desired If HTTPS with own trusted TLS certificate is selected follow instructions in Section 7 2 1 Click the Save button Fi...

Page 57: ...available if the security mode was previously setup as HTTPS with own trusted TLS certificate Click Security in the Navigation panel Click the Edit Certificate button to open the certificate and key...

Page 58: ...very Instructions document For ProtoNode FPC N54 or MB485ETH CG recovery instructions see the MB485ETH CG Next Gen Recovery document If the default unique password is lost then the unit must be mailed...

Page 59: ...ord o User details are hashed and salted NOTE The password must meet the minimum complexity requirements An algorithm automatically checks the password entered and notes the level of strength on the t...

Page 60: ...ncil icon next to the desired user to open the User Edit window Once the User Edit window opens change the User Security Group and Password as needed Click Confirm Once the Success message appears cli...

Page 61: ...rrier 61 Appendix B 6 2 1 Delete Users Click the trash can icon next to the desired user to delete the entry When the warning message appears click Confirm Figure 62 Setup Users Figure 63 User Delete...

Page 62: ...algorithm automatically checks the password entered and notes the level of strength on the top right of the Password text field NOTE If a gateway in the field is updated to a secure gateway the passwo...

Page 63: ...rk settings by clicking the Settings tab and then click the Network tab o Check with the site s IT support that the DNS settings are setup correctly o Ensure that the MB485ETH CG is properly connected...

Page 64: ...tivity and device alert level The color of the button represents the status of one to all three systems Green Normal status Yellow Warning status Red Alarm status Click on the System Status Button to...

Page 65: ...pe SMA Encryption TKIP WPA AES Figure 66 Specifications Appendix C 1 1 Compliance with UL Regulations For UL compliance the following instructions must be met when operating MB485ETH CG The units shal...

Page 66: ...same as the Modbus RTU registers for the serial device If this point list is needed contact technical support The Modbus TCP IP node address of the device is also the same as the Modbus RTU node addr...

Page 67: ...T_count_f Timer AI 4 U16_XXX 003 4 3 X01 3 nvoTimer_XXX SNVT_count_f Flame AI 5 U16_XXX 004 4 3 X01 4 nvoFlame_XXX SNVT_count_f Logstat AI 6 U16_XXX 005 4 3 X01 5 nvoLogstat_XXX SNVT_count_f Sysmins A...

Page 68: ...U32_XXX 022 4 3 X02 22 nvoLko10BrCy_XXX SNVT_count_f Op_Control BI 27 Bit_XXX 032 4 3 X03 32 nvoOpControl_XXX SNVT_switch Aux_1 BI 28 Bit_XXX 033 4 3 X03 33 nvoAux1_XXX SNVT_switch Aux_2 BI 29 Bit_XX...

Page 69: ...XXX SNVT_count_f Sensor 1 Measured Raw Value AI 30 Flt_XXX 029 4 3 X01 29 nvoSen1MsRaw_XXX SNVT_count_f Sensor 2 Measured Raw Value AI 31 Flt_XXX 030 4 3 X01 30 nvoSen2MsRaw_XXX SNVT_count_f Sensor 3...

Page 70: ...I 93 Flt_XXX 092 4 3 X01 92 nvoFt7ErCod_XXX SNVT_count_f Fault 7 Time Of Fault Occ AI 94 Flt_XXX 093 4 3 X01 93 nvoFt7TimFlt_XXX SNVT_count_f Fault 7 Date Of Fault Occ Day Hour AI 95 Flt_XXX 094 4 3 X...

Page 71: ..._count_f Sensor 5 Cut Out Value AI 146 Flt_XXX 145 4 3 X01 145 nvoSn5CtOtVl_XXX SNVT_count_f Sensor 5 Margin Alarm Value AI 147 Flt_XXX 146 4 3 X01 146 nvoSn5MgAlVl_XXX SNVT_count_f Sensor 5 Limit Ala...

Page 72: ...NT_SAFE BV 29 Bit_XXX 022 4 3 X03 22 nvoOUT_IntSf_XXX SNVT_switch OUT_BIT7 BV 30 Bit_XXX 023 4 3 X03 23 nvoOUT_Bit7_XXX SNVT_switch OUT_LO_FIRE BV 31 Bit_XXX 024 4 3 X03 24 nvoOUT_LoFir_XXX SNVT_switc...

Page 73: ...0 Lo Oil Press BV 91 Bit_XXX 040 4 3 X03 40 nvoYZLoOlPrs_XXX SNVT_switch YZ300 Lo Atom Media BV 92 Bit_XXX 041 4 3 X03 41 nvoYZLoAtMed_XXX SNVT_switch YZ300 Lo Gas Press BV 93 Bit_XXX 042 4 3 X03 42 n...

Page 74: ...AV 142 U16_XXX 117 4 3 X01 117 nvoL1Modmax_XXX SNVT_count_f LAG 2 Lag Mode AV 143 U16_XXX 118 4 3 X01 118 nvoL2LagMode_XXX SNVT_count_f LAG 2 Start Delay AV 144 U16_XXX 119 4 3 X01 119 nvoL2StrtDel_X...

Page 75: ...I 16 AI_XXX 018 4 3 X01 18 nvoHoursRun_XXX SNVT_count_f Burner Status AI 17 AI_XXX 019 4 3 X01 19 nvoBrnrStat_XXX SNVT_count_f Trim AI 18 AI_XXX 020 4 3 X01 20 nvoTrim_XXX SNVT_count_f Setpoint AI 19...

Page 76: ..._f Engineers Key 052 AI 80 AI_XXX 102 4 3 X01 102 nvoEngKey052_XXX SNVT_count_f Engineers Key 053 AI 81 AI_XXX 103 4 3 X01 103 nvoEngKey053_XXX SNVT_count_f Engineers Key 054 AI 82 AI_XXX 104 4 3 X01...

Page 77: ...ey115_XXX SNVT_count_f Engineers Key 116 AI 144 AI_XXX 166 4 3 X01 166 nvoEngKey116_XXX SNVT_count_f Engineers Key 117 AI 145 AI_XXX 167 4 3 X01 167 nvoEngKey117_XXX SNVT_count_f Engineers Key 118 AI...

Page 78: ...AI 208 AI_XXX 230 4 3 X01 230 nvoEngKey180_XXX SNVT_count_f Engineers Key 181 AI 209 AI_XXX 231 4 3 X01 231 nvoEngKey181_XXX SNVT_count_f Engineers Key 182 AI 210 AI_XXX 232 4 3 X01 232 nvoEngKey182_...

Page 79: ...XXX SNVT_count_f Fault Log Item 05 Day AI 1045 Log_XXX 044 4 3 X02 44 nvoF05Day_XXX SNVT_count_f Fault Log Item 05 Hour AI 1046 Log_XXX 045 4 3 X02 45 nvoF05Hour_XXX SNVT_count_f Fault Log Item 05 Min...

Page 80: ..._f Fault Log Item 13 Day AI 1109 Log_XXX 108 4 3 X02 108 nvoF13Day_XXX SNVT_count_f Fault Log Item 13 Hour AI 1110 Log_XXX 109 4 3 X02 109 nvoF13Hour_XXX SNVT_count_f Fault Log Item 13 Minute AI 1111...

Page 81: ...21 Fault Num AI 1169 Log_XXX 168 4 3 X02 168 nvoF21FltNum_XXX SNVT_count_f Fault Log Item 21 Condition AI 1170 Log_XXX 169 4 3 X02 169 nvoF21Cond_XXX SNVT_count_f Fault Log Item 21 Year AI 1171 Log_X...

Page 82: ...18 nvoLckotHst4_XXX SNVT_count_f LOCKOUT_HISTORY_5 AV 31 U16_XXX 019 4 3 X01 19 nvoLckotHst5_XXX SNVT_count_f LOCKOUT_HISTORY_6 AV 32 U16_XXX 020 4 3 X01 20 nvoLckotHst6_XXX SNVT_count_f DEVTYP AV 33...

Page 83: ...38 4 3 X03 38 nvoE3Aux5_XXX SNVT_switch E300 Aux 6 BV 69 Bit_XXX 039 4 3 X03 39 nvoE3Aux6_XXX SNVT_switch E300 Low Water BV 70 Bit_XXX 040 4 3 X03 40 nvoE3LoWtr_XXX SNVT_switch E300 Gas Selected BV 71...

Page 84: ...SNVT_switch OUT_MTFI BV 15 Bit_XXX 016 4 3 X03 16 nvoOUT_MTFI_XXX SNVT_switch OUT_Main Fuel BV 16 Bit_XXX 017 4 3 X03 17 nvoOUT_MnFl_XXX SNVT_switch OUT_Pilot BV 17 Bit_XXX 018 4 3 X03 18 nvoOUT_Pilo...

Page 85: ...em Seconds AI 32 U16_XXX 031 4 3 X01 31 nvoSysSec_XXX SNVT_count_f Operating Frequency MCU 1 AI 33 U16_XXX 032 4 3 X01 32 nvoOpFrqMCU1_XXX SNVT_count_f Operating Frequency MCU 2 AI 34 U16_XXX 033 4 3...

Page 86: ...ut History 8 Reason Code AI 71 U16_XXX 070 4 3 X01 70 nvoLH8RsnCd_XXX SNVT_count_f Lockout History 8 Burner State AI 72 U16_XXX 071 4 3 X01 71 nvoLH8BrnSt_XXX SNVT_count_f Lockout History 8 Burner Min...

Page 87: ...istory Data AI 21 U16_XXX 016 4 3 X01 16 nvoLsFlHtDat_XXX SNVT_count_inc_f 2nd to Last Fault History Type AI 22 U16_XXX 017 4 3 X01 17 nvo2FlHtTyp_XXX SNVT_count_inc_f 2nd to Last Fault History Data A...

Page 88: ...XXX 018 4 3 X02 18 nviSrvCdPs19_XXX SNVT_count_inc_f Servo Cmd Position at Speed 20 AV 20 Wrt_XXX 019 4 3 X02 19 nviSrvCdPs20_XXX SNVT_count_inc_f Servo Cmd Position at Speed 21 AV 21 Wrt_XXX 020 4 3...

Page 89: ...53 nviSrvCdPs54_XXX SNVT_count_inc_f Servo Cmd Position at Speed 55 AV 55 Wrt_XXX 054 4 3 X02 54 nviSrvCdPs55_XXX SNVT_count_inc_f Servo Cmd Position at Speed 56 AV 56 Wrt_XXX 055 4 3 X02 55 nviSrvCd...

Page 90: ...8 nvoAT_Setpnt_XXX SNVT_swtich REMOTE BI 24 DI_XXX 009 4 3 X03 9 nvoRemote_XXX SNVT_swtich ABOVE_LIMIT BI 25 DI_XXX 010 4 3 X03 10 nvoAbvLimit_XXX SNVT_swtich EXT2 DI BI 26 DI_XXX 011 4 3 X03 11 nvoE...

Page 91: ...AI 29 S16_XXX 028 4 3 X01 28 nvoIR_Pnt_5_XXX SNVT_count_inc_f IR DATA POINT 6 AI 30 S16_XXX 029 4 3 X01 29 nvoIR_Pnt_6_XXX SNVT_count_inc_f IR DATA POINT 7 AI 31 S16_XXX 030 4 3 X01 30 nvoIR_Pnt_7_XXX...

Page 92: ...ED AI 93 S16_XXX 094 4 3 X01 94 nvoB_IRSenEn_XXX SNVT_count_inc_f FILE B UV SENSOR ENABLED AI 94 S16_XXX 095 4 3 X01 95 nvoB_UVSenEn_XXX SNVT_count_inc_f FILE B IR GAIN SWITCH AI 95 S16_XXX 096 4 3 X0...

Page 93: ...SNVT_count_inc_f LEARNT AVG ON FFT FOR IR POINT 21 AI 158 S16_XXX 159 4 3 X01 159 nvoLnOnIR21_XXX SNVT_count_inc_f LEARNT AVG ON FFT FOR IR POINT 22 AI 159 S16_XXX 160 4 3 X01 160 nvoLnOnIR22_XXX SNV...

Page 94: ...5_XXX SNVT_count_inc_f LEARNT AVG OFF FFT FOR UV POINT 6 AI 215 S16_XXX 216 4 3 X01 216 nvoLnOffUV6_XXX SNVT_count_inc_f LEARNT AVG OFF FFT FOR UV POINT 7 AI 216 S16_XXX 217 4 3 X01 217 nvoLnOffUV7_XX...

Page 95: ...gital Input 13 BI 30 Srv_XXX 029 4 3 X01 29 nvoCurDI13_XXX SNVT_switch Current Digital Input 14 BI 31 Srv_XXX 030 4 3 X01 30 nvoCurDI14_XXX SNVT_switch Current Digital Input 15 BI 32 Srv_XXX 031 4 3 X...

Page 96: ...count_inc_f Servo 7 Current Position AI 94 Srv_XXX 093 4 3 X01 93 nvoSv7CurPos_XXX SNVT_count_inc_f Servo 8 Command AI 95 Srv_XXX 094 4 3 X01 94 nvoSv8Cmd_XXX SNVT_count_inc_f Servo 8 Data Length AI 9...

Page 97: ..._f Lockout History 3 Day AI 157 Srv_XXX 156 4 3 X01 156 nvoLH3_Day_XXX SNVT_count_inc_f Lockout History 3 Year AI 158 Srv_XXX 157 4 3 X01 157 nvoLH3_Year_XXX SNVT_count_inc_f Lockout History 4 Operati...

Page 98: ...NVT_count_inc_f Lockout History 10 Profile Position AI 220 Srv_XXX 219 4 3 X01 219 nvoLH10PrPos_XXX SNVT_count_inc_f Lockout History 10 Error Code AI 221 Srv_XXX 220 4 3 X01 220 nvoLH10ErrCd_XXX SNVT_...

Page 99: ...ofile 3 Max Modulation AI 279 Srv_XXX 278 4 3 X01 278 nvoPrf3MxMod_XXX SNVT_count_inc_f Profile 4 Name AI 280 Srv_XXX 279 4 3 X01 279 nvoPrf4Name_XXX SNVT_count_inc_f Profile 4 Max Modulation AI 281 S...

Reviews: