23
FIGURE 17.
WIRING FOR 95DSS3-1CEXSS and 95DSS3-1CEX-2 scanners (shown with housing cover removed))
8-PIN TERMINAL BLOCK
9-PIN TERMINAL BLOCK
REMOTE FILE SELECTION
The InSight II scanners have four (A,B,C,D) programmable memory files. The user has the option of
storing different scanner setpoints for different operating conditions (e.g. Gas / Oil, Pilot / Main, Low Fire
/ High Fire, etc.) in these files. With RFS selected as “
Line Inputs
”, one or two external switches (sup-
plied by user) will select between the files when the RFS1 or RFS2 wires are connected to 24 vdc (-).
The default is
RFS = “Key Pad”
which allows manual file selection at the scanner keypad only. The
user may also select
RFS = “Comms”
which will allow manual selection at a remote computer running
Fireye software. Fireye recommends the use of shielded cable for the two remote file select switches (or
relays). The switch contacts should be rated for low current operation (3mA dc).
59-546 Cable Color
(if used)
Pin Number of
Terminal Block
Function
59-547 Cable Color
(if used)
Pin Number of
Terminal Block
Function
Red
1
FR1-Relay NO
Brown/Orange stripe
1
Comm - A
Black
2
FR1-Relay COM
Orange/Black stripe
2
Comm - B
Tan
3
FR1-Relay NC
Blue /Black stripe
3
RFS1
Violet
4
Fault-Relay NO
Black/Yellow stripe
4
RFS2
Orange
5
Fault-Relay COM
Red/White stripe
5
4-20 mA OUT(+)(FR1)
Blue
6
FR2-Relay NC
Yellow/Black stripe
6
4-20 mA OUT RTN(-)
Brown
7
FR2-Relay COM
Red/Black stripe
7
4-20 mA OUT(+)(FR2)
Yellow
8
FR2-Relay NO
Black/Orange stripe
8
Power (-) 24 VDC and
4-20 mA OUT RTN(-)
Wiring Notes:
Blue/Red stripe
9
Power(+) 24 VDC
Screw style terminal blocks. Small screwdriver required.
Brown/Black stripe
Cut
(no connection)
Wire Gauge: 24 AWG min., 16 AWG max.
Violet/White stripe
Cut
(no connection)
Wire strip length: 0.375" (9-10mm)
Orange/White stripe
Cut
(no connection)
RFS1 (Blue/Black stripe)
RFS2 (Black/Yellow stripe)
File Selected
Open
Open
A
Closed
Open
B
Open
Closed
C
Closed
Closed
D
9 Pin terminal Block
8 Pin terminal Block