18
SCANNER DISPLAYS (for standard / non-CEX models)
Scanner Display, P/N 95DISP-1, 95DISP-1-SS
P/N 95DISP-1 is a two-line by sixteen-character alpha-numeric VFD Display with a five-pushbutton
keypad. The 95DISP-1 is installed by the user onto the end of the standard scanners enabling the user
to view and change the operating parameters and setpoints at the scanner itself. The 95DISP-1-SS is
factory installed into the 95DSS3-1CEXSS and 95DSS3-1CEX-2 scanners.
Infrared Transmitter, P/N 95WIDISP-2
P/N 95WIDISP-2 is an Infrared Transmitter, installed by the user onto the end of the scanner instead
of a display. The 95WIDISP-2 transmitter provides infrared wireless communications to a model
95WIHH-2 hand-held remote communications tool.
Hand-Held Remote Communications Tool, P/N 95WIHH-2
P/N 95WIHH-2 is hand-held infrared remote communications tool. It contains an alpha-numeric dis-
play and pushbutton keys enabling the user to view and change the operating parameters and set-
points of an InSight II scanner when standing in line-of-sight of the scanner. The InSight II scanner
must be fitted with the optional 95WIDISP-2 infrared Transmitter.
Blank Cover, P/N 61-7347-1
P/N 61-7347-1 is a Blank Cover used to maintain environmental ratings when neither the 95DISP-1
nor 95WIDISP-2 is installed. With the 61-7347-1 installed, the operator interface must either be via
"Fireye Explorer" pc software, or by temporarily installing a 95DISP-1 or 95WIDISP-2.
Refer to bulletin CU-116 for 95DISP-1, 95DISP-1-SS, 95WIDISP-2, and 61-7347-1 installation
instructions.
Note: Model 95DSS3-1CEX includes the 95DISP-1 Display.
Models 95DSS3-1CEXSS and 95DSS3-1CEX-2 include the 95DISP-1-SS Display.
Model 95DSS3-1WICEX includes the 95WIDISP-2 Infrared Transmitter.
Model 95DSS3-1CEX-ND includes the 61-7347-1 Blank Cover.
SCANNER WIRING
To reduce electrical noise interference, take precautions to keep the scanner cable away from any high
inductive wiring associated with high inductive loads or high voltage, high energy spark ignition sys-
tems.
CAUTION: The flame scanner requires 24 Vdc power for operation. Connection to a 24 Vac
or 120 Vac power source will damage the scanner. Refer to wiring diagrams.
External 0.5 Amp slow-blow fuses are recommended to protect Flame Relay and Fault Relay
contacts
All wiring to the scanner should be rated at 105°C. For runs less than 1000 feet, the use of
Fireye Scanner Cable, P/N 59-546, (8 wire) and P/N 59-547, (12 wire) is recommended. For
runs in excess of 1000 feet, consult the factory.
CAUTION - Damage to electronic components through electrostatic discharge (ESD)
Note: Before touching the internals of the InSight II scanner installers can discharge any static built
up on their body by touching the outside of the scanner housing if the ground is already attached. If
the scanner isn’t already grounded, the installer could touch a nearby object that is earthed.