55
SELECT to Exit BACK to MAIN
Returns to Main Status Menu
THE IR and UV SETTINGS MENUS
FIGURE 33.
IR SETTINGS MENU LOOP (UV is similar)
R1AIR-BAND(Freq)
70Hz
R1AIR-USER GAIN
1
R1AIR-FEG LRNED
255
< SELECT to Exit
To Previous Menu
To Manual
Config Menu
< SELECT to Exit
BACK to MAIN
To MAIN
Status Menu
R1AIR-MAX FEG
255
R1AIR-MIN FEG
5
< SELECT to Exit
BACK to CONFIG
To Config
Menu
R1AIR-BAND(Freq)
000 70Hz
R1AIR-USER GAIN
000 1
R1AIR-FEG LRNED
255 255
R1AIR-MIN FEG
255 5
R1AIR-MAX FEG
255 255
Display Legend
R1AIR-BAND(Freq)
XXX 70Hz
FILE A
IR
Sensor
Flame
Relay 1
Parameter
Value Saved
Parameter
Name
Real-Time
Flame Signal *
* If setting an FEG value,
the real-time FEG is shown
P
SELECT Key
UP Key (Scrolls through menu, counter clockwise)
DOWN Key (Scrolls through menu, clockwise)
PROGRAM Key
CAUTION: On
Engr Code 40
or lower
, do
not
set IR BAND (e.g., R1AIR-BAND) or
UV BAND (e.g., R1AUV-BAND) parame-
ters on either flame relay (R1 or R2) on
any file (A,B,C, or D) to 165, 171, or 179.