58
INSIGHT II FACTORY DEFAULT SETTINGS, USER FILES A,B,C,D and Factory File F3
PARAMETER
DEFAULT VALUE
ALLOWABLE VALUES
Config Menu:
Remote File Sel
Key Pad
Key Pad, Line Inputs, Comms
PASSWORD
0205
0000-9999
FS Squelch Msgs
Do NOT Display
Display, Do NOT Display
IR GAIN RANGE
LOW
HIGH, MED
1
, LOW+2
2
, LOW+1
2
, LOW
UV GAIN RANGE
LOW
HIGH, MED
1
, LOW
1
(“MED” range available in engineering code 05 or higher)
2
(“LOW+2”, “LOW+1” ranges available in EC 09 or higher)
4/20mA Config Menu:
FR1 4/20 SELECT
Flame QUALITY
Flame QUALITY, Flame SIGNAL
FR1 4/20 MAP VAL
100
For Flame Quality: 40-100
For Flame SIGNAL: 400-999
FR2 4/20 SELECT
Flame QUALITY
Flame QUALITY, Flame SIGNAL
FR2 4/20 MAP VAL
100
For Flame Quality: 40-100
For Flame SIGNAL: 400-999
Date/Time Menu:
YEAR
2010
2008-4095
MONTH
JAN
JAN,FEB,MAR,APR,MAY,JUN,JUL,AUG,SEP,OCT,NOV,DEC
DAY OF THE MONTH
01
01-31 (dependent on current value of MONTH)
HOUR (0-23)
00
00-23
MINUTES (0-59)
00
00-59
SECONDS (0-59)
00
00-59
COMMS SETTINGS Menu:
MODBUS ADDRESS
247
001-247
MODBUS BAUD
19200
4800, 9600, 19200
MODBUS PARITY
8/N/1
8/N/1, 8/E/1, 8/N/2, 8/O/1
Man. Config FR1 Menu:
R1- SENSOR SLECT
IR & UV SENSORS
IR & UV SENSORS, IR SENSOR ONLY, UV SENSOR ONLY
R1- FFRT
1
1,2,3,4, 5*, 6* *not FM class 7610 approved
R1- ON THRESHLD
40
5-100
R1- OFF THRESHLD
20
0-95
R1- On Time Dely
1
1,2,3,4,5,6
FR1 IR Settings Menu:
R1 IR-BAND (Freq)
179Hz
23,31,39,46,54,62,70,78,85,93,101,109,117,125,132,140,148,
156,164,171,179Hz
R1 IR-USER GAIN
1
1-31
R1 IR-FEG LRNED
5
5-255