12
7.
In larger multi-burner type applications such as power, kiln or refinery burners, it is recognized
that there may be several obstructions within the scanner overall range of view. The same princi-
ple of adjusting the scanner such that the flame is within the center of its field of view applies.
Use of a swivel mount allows the scanner to be adjusted to target the flame within the center of
the scanner range of view. (see obstructed view in figure 6 above)
8.
For ease of use, the scanner should be installed on the sight pipe so the VFD display (if used)
can easily be read.
Note: Operation of the VFD display is independent of position.
9.
The scanner lens must be kept free of contaminants (oil, ash, soot, dirt) and the scanner housing
temperature must not exceed its maximum rating of 150°F (65°C). Excessive temperatures will
shorten scanner life. Both requirements will be satisfied by a continuous injection of purge air at
either the 3/8” housing inlet or the 1” “Y” connection ahead of the swivel mount as shown in
Figures 7, 8 and 9.
Note: Internal scanner temperature is available via the VFD display. See “Status Menu” under
“Programming the Scanner.”
The scanner mounting may be made with provision for purge air through only the 3/8” opening as
shown in Figure 9 or for purge air through either the 3/8” opening or the 1” “Y” connection as shown
in Figure 8. In the latter arrangements, normally only one of the two connections is provided with
purge air and the other connection is plugged. When a sealing coupling is used as shown in Figure 7,
the 1" “Y” connection is used for the purge air and the 3/8” opening is plugged.
It is good practice to use the sealing coupling (P/N 60-1199 with NPT threads) on all installations to
insure against unwanted furnace pressures from damaging the scanner lens.
Under normal conditions, with clean burning fuels and moderate ambient temperature conditions,
purge air flow of approximately 4 SCFM (113 l/min) is generally adequate. Up to 15 SCFM
(425 l/min) may be required for fuels that produce high levels of ash or soot, or for hot environments
to maintain the scanner’s internal temperature within specification.
MECHANICAL ACCESSORIES
Surface Mounting Flange (Required)
Standard:
Cast aluminum
with gray polyester powder coat finish. Contains an integral heat-insulating female
thread insert (external heat-insulating nipple not required).
P/N 60-2919-1 1" NPT female pipe mount with 3/8” NPT female cooling air connection.
P/N 60-2919-2 1" BSP female pipe mount with 3/8” BSP female cooling air connection.
Optional:
316 Stainless Steel
with zinc primer, gray epoxy midcoat and polyurethane top coat finish. Does not
contain heat-insulating insert.
P/N 60-2692SS 1" NPT female pipe mount with 3/8” NPT female cooling air connection.
P/N 60-2693SS 1” BSP female pipe mount with 3/8” BSP female cooling air connection.
Optional:
Cast aluminum
with grey polyester powder coat finish. Does not contain heat-insulating insert.
P/N 60-2692-4, 1" NPT female pipe mount with 3/8" NPT female cooling air connection.
P/N 60-2693-4, 1" BSP female pipe mount with 3/8" BSP female cooling air connection.
Swivel Mount (Optional)
The scanner swivel mount, P/N 60-1664-3 (NPT) (see Figure 9, Item A), is used to adjust the scanner
sighting angle after the scanner has been installed, The swivel mount is shown in Figures 7, 8, and 9.
Sealing Coupling with Quartz Window (Optional)
The sealing coupling, P/N 60-1199-x (see Figure 10, Item D), is used whenever a coupling or a seal
is required for scanner piping. The quartz window blocks furnace pressure, hot gases and soot from
coming in contact with the scanner and contaminating the lens. P/N 60-1199-1 has a 1" NPT thread,
p/n 60-1199-2 has a 1" BSP thread. When the sealing coupling is used, a 1 inch “Y” fitting must be
used downstream of it for connection of a purge air supply (plug 3/8”opening).