27
INSIGHT II MENU STRUCTURE
For ease of operation, the InSight II scanner contains five primary menus (or loops) accessed via the
keypad and viewed on the scanner’s display.
1. MAIN STATUS MENU
The Main Status menu is the default display. Use the UP and DOWN buttons to scroll through the
menu and view the current operating status. No operating parameters can be changed from the Main
Status menu. To change any setpoint, you must select the Configure Menu option and then enter a
four digit password to enter the Configuration menu. Error History can also be viewed from the
Main Menu.
Note:When power is applied, the following splash screen is displayed for 2 seconds:
"Display CRC=xxxx, Display Rev= xx".
After 2 seconds, the display will revert to the first display of the Main Status menu:
"1=OFF 2=0FF F=A, FQ 1:000 2:000".
2. CONFIG MENU
The Config Menu accesses all of the sub-menus, and setpoints for the InSight II scanner. The Config
menu is entered from the Main menu after first entering a four-digit password. From the CONFIG
menu the user can enter the AUTOMATIC CONFIG and MANUAL CONFIG and other menus.
3. AUTOMATIC CONFIG MENU
From the Automatic Config Menu, the user views the flame signal intensity while physically aiming
the scanner for optimum signal. With the target burner ON (firing), and the scanner properly aimed,
the user can command the InSight II scanner to Learn the Flame ON condition. With the target
burner OFF (not firing), the user can command the InSight II scanner to Learn the Flame OFF condi-
tion. The scanner will then automatically select the optimum flame relay and sensor setpoints. The
Automatic Config Menu is entered from the CONFIG menu.
4 & 5. MANUAL CONFIG MENUS
There are two Manual Config Menus, one for FR1 (flame relay 1) and the other for FR2 (flame relay
2) values. From the Manual Config Menu the user would select the desired FFRT (Flame Failure
Response Time), and On Time Delay for the flame relays. From this menu, the user may also manu-
ally adjust all other flame relay and sensor setpoints. The Manual Config Menu is entered from the
CONFIG menu.
CAUTION: On
Engr Code 40
or lower
, do
not
set IR BAND (e.g., R1AIR-BAND) or UV
BAND (e.g., R1AUV-BAND) parameters on either flame relay (R1 or R2) on any file
(A,B,C, or D) to 165, 171, or 179. On Engr Code 40 or lower, these frequencies, if set in
combination with manually adjusted high user gains (e.g., R1AIR-GAIN = 30) and/or
lowered switching thresholds (e.g., R1A ON-THRESHLD = 15) may simulate the pres-
ence of flame when flame is not present. This combination of settings may cause your
scanner to indicate a false flame condition.