Panel Operation
7.3.5.1.6 S
ERVICE
M
ENU
–
C
ONFIG
–
C
HANGE
–
A
NALOG
P
OINT
Once you have selected an Analog addressable point from the list or entered directly, you will be on modify
Analog point screen. This screen will be different depending on what type of Analog addressable point is selected.
I.e. Detector, Input Module or Output Module.
Detectors:
Actions:
DAY MODE
Press the
BACKSP
button to delete an incorrect
character.
Press the
ENTER
button to step through options.
Press the
YES
or
NO
buttons when highlighted
to answer Y/N options.
Use external QWERTY keyboard to edit
descriptors and zone type.
The numerical keypad can be used for numerical
entries.
When entering device type a numerical pick list
will appear at the bottom of the screen.
Refer to appendix for more information on options
and sensitivity settings.
You will be prompted Yes/No to save changes
when finished.
65
•
•
•
•
SENSITIVITY 1-9: (1 is most sensitive)
Day Alarm
5
Day Pre-Alarm
4
Night Alarm
1
Night Pre-Alarm
1
•
•
ENTER
•
BACKSP
AFP-2800/2802 Manual
– P/N DOC-01-011
20 JULY 2002 14:44:37
SELECTED POINT : L1D1
L1D1
> APARTMENT 1 BATHROOM
DEVICE TYPE
> PHOTO
ZONE NO.
> 2
ZONE TYPE
> SMOKE
ALARMED? (Y/N)
> Y
LATCHED? (Y/N)
> Y
AVF?
(Y/N)
> N
ANALOG MENU – PROG
A = 0
F = 0
I = 0
N = 0
•