Appendix
Actual Fault
Code
Possible causes
Displayed
Beam Blocked
FAULT (F024)
Beam Detector Fault - SOMETHING HAS COME BETWEEN THE D
ETECTOR’S
beam and its reflector.
Alignment Mode
FAULT (F025)
Beam Detector Fault - A beam detector is in configuration mode.
Device Disabled
FAULT (F026)
Not used on AFP-2800/2802.
Zone Disabled
FAULT (F027)
Not used on AFP-2800/2802.
Initialisation Mode
FAULT (F028)
Beam Detector Fault - A beam detector is running through its
initialization sequence.
Incorrect Position
FAULT (F029)
Beam Detector Fault -
Over Range
FAULT (F030)
Not used on AFP-2800/2802 - FMM-4-20.
Under Range
FAULT (F031)
Not used on AFP-2800/2802 - FMM-4-20.
Device Inhibit
FAULT (F032)
Not used on AFP-2800/2802 - FMM-4-20.
No Threshold
FAULT (F033)
Not used on AFP-2800/2802 - FMM-4-20.
Programmed
Trouble 1
FAULT (F034)
Not used on AFP-2800/2802 - FMM-4-20.
Trouble 2
FAULT (F035)
Not used on AFP-2800/2802 - FMM-4-20.
Comms Loss
FAULT (F036)
Not used on AFP-2800/2802 - FMM-4-20.
Command Failed
FAULT (F037)
Not used on AFP-2800/2802.
Thermistor Fault
FAULT (F038)
The thermistors are not functioning properly on a FSC-851 detector.
This trouble is generated for FlashScan mode only.
IR Fault
FAULT (F039)
The infrared element is not working properly on a FSC-851 detector.
This trouble is generated for FlashScan mode only.
IR Light Saturation
FAULT (F040)
The infrared sensor on a FSC-851 detector is saturated.
CO 6 Month Of Life
FAULT (F041)
The CO (carbon monoxide) detection element on a FSC-851 detector
has six months left to expiration.
CO Life Expired
FAULT (F042)
The CO (carbon monoxide) detection element on a FSC-851 detector
has expired.
CO Fault
FAULT (F043)
The CO element on a FSC-851 detector is not working properly. This
trouble is generated for FlashScan mode only.
AFP-2800/2802 Manual
– P/N DOC-01-011
110
Summary of Contents for AFP-2800
Page 139: ...Appendix 9 12 PANEL EXPANSION RELAYS AFP 2800 2802 Manual P N DOC 01 011 139...
Page 156: ...Notes...
Page 157: ......