Panel Operation
7.3.8.2 S
ERVICE
M
ENU
–
D
IAGNOSTICS
–
D
BASE
Performs a test of Database RAM, this will clear all database information etc. The system will take several
seconds to re-acquire all system information but will not destroy any configuration information.
7.3.8.3 S
ERVICE
M
ENU
–
D
IAGNOSTICS
–
F
LASH
This will perform a full CRC check (up to 30 seconds) on the Flash memory to confirm correct operation.
7.3.8.4 S
ERVICE
M
ENU
–
D
IAGNOSTICS
–
R
ELAY
This mode will test the correct operation of local relays by cycling through them one at a time. Pressing any button
stops the test.
7.3.8.5 S
ERVICE
M
ENU
–
D
IAGNOSTICS
–
XR
ELAY
This mode will test the correct operation of expansion relays within the panel by cycling through them one at a
time. Pressing any button stops the test.
7.3.8.6 S
ERVICE
M
ENU
–
D
IAGNOSTICS
–
LED
This mode will test the correct operation of panel LED and LCD display by randomly flashing LEDS and filling the
LCD with data. Pressing any button stops the test.
7.3.8.7 S
ERVICE
M
ENU
–
D
IAGNOSTICS
–
M
ODULE
This mode will perform tests on field modules to ensure correct communications and operation.
Actions:
•
Use the
UP
and
DOWN
buttons to scroll through
options and then use the
SELECT
button to
select the highlighted option
(or button
1
to
3
from the numeric keypad)
•
Press the
BACK
button to return to the Service
Menu screen.
AFP-2800/2802 Manual
– P/N DOC-01-011
83
DAY MODE
20 JULY 2002 14:44:37
1)
AZF . . . . AUTOTEST ALL AZFS ON MODULE
2)
DOUT . . . .AUTOTEST ALL Dig. OUTS ON MODULE
3)
DBASE . . . DISPLAY MODULE DBASE
USE UP/DOWN BUTTONS TO SELECT A FUNCTION
UP
DOWN
SELECT
BACK
MODULE TEST MENU
A = 0
F = 0
I = 0
N = 1
Summary of Contents for AFP-2800