System Capacity And Expandability
6 S
YSTEM
C
APACITY
A
ND
E
XPANDABILITY
6.1
B
ASE
S
YSTEM
Item
Description
Notes
Communications Ring
RS485 communications ring to support
Up to 100 Field Modules
Up to 50 Annunciators
8 System Outputs
4 x Monitored Outputs.
Fault output is normally
Bell Output
energised using V5.00
3 Additional
and above firmware.
programmable outputs
4 x Clean contact relays
Max contact rating of all
General Alarm Output
relays 1A @ 30Vdc.
General Fault Output
2 x programmable outputs
Power Supply
2.6 A power supply and battery
A larger power supply
charger
may be required if total
Fused 27.3Vdc outputs
module load exceeds
2A. Power supplies up
to 11.7A are available.
2 LOCAL
AZF’S
AZF 1
AZF 2
2 RS232 communication Laptop interface
ports
System event printer
Remote terminal mode
Keyboard Interface
PS2 QWERTY IBM PC keyboard
System Memory
Approx. 4300 Named points
Approx. 4000 Control scripts
4000 History events
6.2
E
XPANSION
PCB
S
Item
Description
Notes
Loop Interface Module
Interface module to communicate with
Each Analog
(LIM)
up to 5 x pairs of Notifier LCM/LEM
addressable loop
modules. I.e. total of 10 FlashScan
supports up to 159
Analog addressable loops for AFP-
detectors and 159
2800 and a total of 4 CLIP Analog
addressable modules
addressable loops for the AFP-2802.
using the Notifier
FlashScan protocol or
99 detectors and 99
modules using the CLIP
protocol.
Network Interface
Interface module to communicate with
AFP-2800 only.
Module (NIM)
the Network Control Module (NCM)
AFP-2802 does not
support Networking.
Panel Expansion Relays Relay card with 8 relays
– contact
Up to 8 IFS-803/IFS-717
(IFS803 or IFS-717)
rating is 1A @ 24Vdc
8-way relay boards can
be added
AFP-2800/2802 Manual