System Capacity And Expandability
6.3
A
NALOG
A
DDRESSABLE
L
OOPS
Item
Description
Loop Control Module
Loop Controller for Loops 1,3,5,7,9
(LCM/ELC)
Loop Expander Module
Loop Controller for Loops 2,4,6,8,10
(LEM)
6.4
A
NNUNCIATORS
Item
Description
ACM32 Annunciator
32 Red LED
ACM16AT Annunciator
16 x Pushbutton inputs
16 x Red LED
16 x Yellow LED
SCS-8 Annunciator
8 x 3 Position switches
8 x Red LED
8 x Yellow LED
8 x Green LED
1 x Fire Trip (A/C) Reset switch
1 x Fire Trip (A/C) Activated/Latched LED
SCS-8L Annunciator
24 x LED outputs & 25 digital inputs
LDM-32 Annunciator
32 x LED outputs (Open Collector)
LDM-R32 Annunciator
32 x Relay outputs rated to 1A @ 30Vdc
6.5
F
IELD
M
ODULES
Item
Description
AZM-8
8 x AZF inputs (4k7 EOL resistor)
4 x Programmable Relay Outputs
Fan Controller (FAN-C)
3 x Inputs (Opto-isolated, not monitored)
3 x Programmable Relay outputs
The RS485 signal is
regenerated at each
field module.
Note:
Please note that the FAN-C module has been discontinued and will not be supplied for new installations.
When annunciators or field modules are powered from external power supplies, use a separate conductor to
connect the main power supply common terminal (-0V) to the remote power supplies common terminal (-0V).
AFP-2800/2802 Manual
– P/N DOC-01-011
19
Notes
Max 5 per AFP-2800
Max 1 per AFP-2802
Max 5 per AFP-2800
Max 1 per AFP-2802
LEM
“PIGGYBACKS”
under the LCM.
Notes
A maximum of 50
annunciators can be
connected to the
communications ring.
Notes
A maximum of 100
field modules can be
connected to the
communications ring.
Larger/external power
supplies and separate
feeds are required for
systems with a large
number of modules or
long cable runs.