Compatible Devices
5.3
C
OMPATIBLE
B
ATTERIES
In general, any Sealed Lead Acid (SLA) battery, or Wet Lead Acid battery designed for stationary use is
compatible with the AFP2800/2802 Fire Indicator Panel. The use of Nickel Cadmium batteries is not
recommended.
Manufacturer
Type
Number
Voltage
Capacity (Ah)
Qty Required
Olympic Batteries
SLA
CJ12-7
12
7
2
Olympic Batteries
SLA
CJ12-12
12
12
2
Olympic Batteries
SLA
CJ12-18
12
18
2
Olympic Batteries
SLA
CJ12-26
12
26
2
Olympic Batteries
SLA
CJ12-33
12
33
2
Olympic Batteries
SLA
CJ12-40
12
40
2
Olympic Batteries
SLA
CJ12-85
12
85
2
Olympic Batteries
SLA
CJ12-100
12
100
2
NOTES:
Automotive batteries must not be used. There is a risk of explosion if battery is replaced by an incorrect type.
Dispose of used batteries according to Manufacturer Instructions
The use of Nickel Cadmium batteries is not recommended.
The batteries could be seriously and permanently damaged if they are permitted to discharge below 20V DC
when placed in series.
The NPS series of power supplies will only charge the battery if the terminal voltage is above 12V when
measured across 2 batteries in series.