Panel Operation
7.3.4.8
S
ERVICE
M
ENU
–
I
SOLATE
–
G
ROUP
I
SOLATE
F
ROM
P
OINT
Single Push Button Isolate Overview
This is a particularly useful feature for setting up single push button isolates for routine testing purposes.
THE
“SINGLE PUSH BUTTON ISOLATE” METHOD CAN isolate any number of points on the system.
Pressing the button (typically on an ACM16AT annunciator) the first time will automatically isolate all the points in
the isolate script. Pressing the button a second time will de-isolate all the points in the isolate script.
Note:
An isolated point is seen as inactive by the panel and hence, in a logic programming script, it will return the
Note:
The annunciator button that is being used to initiate the isolate must be a non-latching button. ie. the Dip
Switch on the ACM16AT annunciator must be set to OFF. The minimum time between isolate and de-isolate
pushbutton action is 5 seconds.
How to configure single push button isolates:
From this menu option the panel will list all the Digital Inputs on the system where you can then assign the
activation of the digital input to perform an isolate of multiple points on the system.
Firstly you must select the digital input used to trigger the isolation process from the list below.
Actions:
•
Use the
UP
and
DOWN
buttons to scroll through
Input points.
•
Pressing the
SELECT
button will take you to the
“ISOLATE RANGE” SCREEN WHERE YOU ENTER IN ALL THE
points for this button press to isolate. (see below)
AFP-2800/2802 Manual
– P/N DOC-01-011
57
value FALSE (or TRUE if the NOT function is applied to it within the script).
If the input being used to trigger the isolate is an ACM16AT button, the system will automatically write scripts for
THE CORRESPONDING YELLOW AND RED
LED’S ON THE ACM16AT AS FOLLOWS. RED = any point in the isolate list is in
alarm. Yellow = all points in isolate list are isolated.
If the points are isolated by an ACM16AT press button action and then one of the points is de-isolated via the
menus the next time the ACM16AT button is pressed it will ensure ALL points are isolated.
DAY MODE
20 JULY 2002 14:44:37
SELECT A POINT TO ISOLATE A GROUP:
01.010.I1 SPF 1 RUNNING
x
01.010.I2 SPF 1 FAULT
01.010.I3 (FANC)
01.101.I1 BUTTON 1 ON 16AT
01.101.I2 BUTTON 2 ON 16AT
01.101.I3 BUTTON 3 ON 16AT
01.101.I4 BUTTON 4 ON 16AT
01.101.I5 BUTTON 5 ON 16AT
01.101.I6 BUTTON 6 ON 16AT
01.101.I7 BUTTON 7 ON 16AT
01.101.I8 BUTTON 8 ON 16AT
01.101.I9 (ACM16AT)
01.101.I10 (ACM16AT)
01.101.I11 (ACM16AT)
01.101.I12 (ACM16AT)
01.101.I13 (ACM16AT)
01.101.I14 (ACM16AT)
01.101.I15 (ACM16AT)
01.101.I16 (ACM16AT)
UP
DOWN
SELECT
BACK
GROUP ISOLATE/DE-ISOLATE
A = 0
F = 0
I = 0
N = 1