Panel Operation
7.3.3.10
S
ERVICE
M
ENU
–
L
IST
–
L
IST
–
D
OUT
This screen will list all the digital outputs (relays) in the system. Digital outputs consist of local panel relays, field
module relays, expansion relays (XRnn) and annunciator outputs.
The display shows the point number (Ring.Module.I/O format) and the point description. In addition, the current
state of the point is displayed. Unnamed points use the associated field module type as their description.
Actions:
•
Use the
UP
and
DOWN
buttons to scroll through
Output points.
•
When highlighting an output point, Pressing the
TEST
button will take you into the test menu for
outputs where you can toggle the output on/off for
testing purposes. Please note that during this test
process, ALL script processing is paused. (Refer to
Page 73 for more details on Dout test page)
•
Pressing the
CHANGE
button will take you to the
modify point screen (refer to page 61)
•
Pressing the
BACK
button will return you to the list
menu screen.
In the above example, the following abbreviations of STATUS apply.
Status
Meaning
Abbreviation
I
Isolated
F
Fault
X
Activated
Note:
You can also use the arrow keys, the Page Up and Page Dn keys on an external keyboard for scrolling
functions.
AFP-2800/2802 Manual
– P/N DOC-01-011
45
DAY MODE
20 JULY 2002 14:44:37
USE UP/DOWN BUTTONS TO SELECT AN O/P:
00.004.01 BELL OUTPUT
00.004.O2 WARNING SYSTEM
00.004.O3 A/C TRIP
00.004.O4 (LOCAL RELAY)
00.004.O5 GENERAL ALARM OUTPUT
00.004.O6 COMMON FAULT OUTPUT
x
00.004.O7 COMMON ISOLATE OUTPUT
x
00.004.08 (LOCAL RELAY)
01.001.O1 LEVEL 1 OUTPUT
01.001.O2 LEVEL 2 OUTPUT
01.001.O3 LEVEL 3 OUTPUT
01.001.O4 (AZM8)
01.002.O1 (AZM8)
01.002.O2 (AZM8)
01.002.O3 (AZM8)
01.002.O4 (AZM8)
UP
DOWN
TEST
CHANGE
BACK
DIGITAL OUTPUT LIST
A = 0
F = 2
I = 1
N = 0
Summary of Contents for AFP-2800
Page 139: ...Appendix 9 12 PANEL EXPANSION RELAYS AFP 2800 2802 Manual P N DOC 01 011 139...