500-IDx 

Conventional Fire Detectors with Siren! 

 

 

Fig. 1:

 Detector 500-IDx, x: O=Optical, I=Ionic, T=Temp. 

 

Description 

ICAS Model 500-IDx is a system detector series to be connected with a 
standard EN54 classified fire central. The detectors are equipped with 
digital signal handling and advanced filter and automatic adjustment of 
sensitivity. The detector series is developed for dwellings, accommodation, 
bed and breakfast places, offices etc. as a system detector connected to an 
EN54 fire central. 
 
When the detector moves from normal to fire alarm, then the current will 
increase.  OPTO-output will be activated and the RED led have fixed light 
until the detector is reset.  
 
The detector has an integrated siren  (85db/3m), which is controlled from 
the fire central or locally from the detector via terminal OPTO. This will be 
switched to 0V when the detector goes into alarm. 
 

Automatic Testing & Sensitivity control (ATS)  

Improved reliability by introducing Automatic Test and Sensitivity control 
to keep the sensitivity at the correct level during the lifetime of the detector. 
The built in micro-controller is also used to communicate with an integrated 
diagnostic system DS500, as well as handling all internal test and 
diagnostics. The detector sends signal fault via LED’s (ref. table page 2). 
 

Advanced Digital Signal-filtration (ADS)

  

This solution guarantees a correct signal handling and reduce nuisance, 
false alarms and give improved immunity against EMC. All the important 
events, i.e. alarms and fault, will be saved to a memory, which can save the 
last 32 events in order of appearance. It has no clock function. 
 

Read the events in each detector from your PC! 

Optional equipment Diagnostic System DS500 for checking the detectors 
via usb-input on your PC. DS-500 is used to read the data from the detector 
memory (eeprom) in a service situation. The system will identify the 
detector and all the data will be sent to the PC for investigation by service 
people, be printed, sent to service-centre or saved. 

 
500-IDX series type of detectors: 

500-IDI:   Ionical chamber, environmental friendly! (3kBq only) 
500-IDO: Optical chamber 
500-IDT: Heat detector with fixed temp. + Rate of Rise function 
 

Terminal-description: 

1: 

+U      (Conn terminal 9V-24V DC) 

2:    0V       (0V connection to next detector in loop) 
3:    0V       (0V from fire central)  
4: 

OPTO (Open collector (in alarm drop to 0V)  

5: 

-SIR    (Sirene  -) 

6: 

+SIR    (Sirene  +) 

Note:

 0V-connectors (connector 2 & 3) make it possible to supervise that 

the detector is connected in the loop 

 

 

Fig 2:

 Standard Base and release mechanism 

 
 

Installation 

1.  Choose the best place to fix the detector. It shall be mounted in the 

ceiling. Min. 0,5m from walls, max. 1,5m from bedroom door and 
min. 1m from light point or other electrical equipment or ventilation 
outlet/fans. 

2.  Use 2 screws to fix the base and terminate the cable to terminals.  

Use terminal 3 (0V) from fire central and terminal 2 (0V) for next 
detector. This to obtain loop fault if a detector is not in its base. 
Note! Valid only for supply from fire central where it’s used 
common wires for power and alarm.  

3.  Place the detector head in the Base by aligning the two marks, see 

fig 2. Then turn the head clockwise approx. until locked. 

4.  Repeat 1–4 for all the detectors in the system. 
5.  Do not start up the detectors in an environment with smoke. (The 

sensitivity can be wrongly set). 

6.  Turn on the power at fire central. 
7.  During the start up time, the detector will give 2 short yellow blink 

every 4. sec. in 40 sec. dependent of the detector in the 500-IDX 
series.  

8.  To remove the detector, use a small screwdriver into the locking 

opening in the base. (See fig 2), and turn anti-clockwise. 

 

 

 

 

 

Fig 3:

 Relay Base. (7=Nc, 8=Com, 9=No) 

 
Relay Base: 

If a relay is needed i.e. for use with a burglar alarm system or to control 
external signals, a relay base is used. 
 
 
 
 