Manual_500-IDx_Eng.doc 

Side 2/5 

 

rev. 24.03.11 

Test 

Sampling is done every 4 sec. If during this period smoke is detected, the detector will be sampling every second before an alarm is being released. If the 
amount of smoke is reduced, or what look like smoke is reduced, the detector will not release an alarm. 
The smoke detector should be tested regular with test gas using a small box covering the detector after it has been sprayed. After approximately 4 seconds, the 
red led will start blinking every second. And shortly after it will switch to steady red light and activate the fire alarm. Make sure the test gas is kept in the 
detector by keeping a cover over the detector during this period of approx. 10 seconds. After alarm the detector must be reset, by removing the power at the 
loop in approx. 2 seconds. The system can be activated again when all test gas is removed from the tested detector. 

NOTE! The LED on the detector is NOT a push button, and shall not be pressed! 

 

Siren 

The siren/buzzer is integrated in the detector, but electrically isolated from it. At the base it is 2 terminals for the siren connection. -Sir (5) & +Sir (6). Siren 
voltage is 12V to 24V. The connection is polarity protected. Filter against EMC is a part of the solution. 
 

Maintenance 

The detector shall be maintained with regularity, especially against dust or other airborne particles included insects. If it is suspected insects inside the detector, 
the detector can be put into a clear airtight plastic bag for 24 hours, to see if any insects will get out. Be aware that dirty environment do make a wear and tear 
situation on the detector, and after some years they will be signalling time for change-out!!   
 

Detector status: 

Signal-colour 

Signal-type 

Status detector 

Action / Comments 

No Light 

None 

- Normal operation 
- Heat/Smoke sensitivity tests every 4sec. 
- Complete detector test every 4 sec. 

 

Yellow 

2 short blink every 4. 
sec. up to 40 sec. 

- Start up detector. 
- Start up or registration in memory 

- Blinking until detector chamber is stabilised. Can vary from 

1 to 40sec.dependig of detector type. 

 

Blink every 4. sec. 

- Chamber / Sensor faulty 
- Program Faulty (Check-sum error) 
- Event saved to memory 
- Fault counter in1. 

- Rengjør, eventuelt bytt detektor 
- Remove power for approx.1min.Change the detector if still 

not working. 

 

4 short blink in intervals 

- ”Watch-Dog” control detects a stalled 

program. 

- Smoke/Heat sampling is done  
- The event being stored in memory 
- WD-counter increases with +1. 

- ”Watch-Dog” checks every 4.sec. If program freeze, it will 

restart the detector automatically. 

- Remove power from detector for 1 min. If this is not 

working, remove and change detector.  

Red 

One blink every 1. sec. 

- Pre alarm. Smoke has been detected. 

- After first smoke detection, the sampling increases  from 4 

to 1 sec. 

 

Steady RED Led 

- The current in the loop increases and activate 

Alarm and OPTO-output drops to 0V. 

- Event is saved 
- Alarm-counter inc1 

- When reason for alarm is found and there is no present fire, 

the detector must be reset by removing the power for 2 
seconds. 

 

Blink every10 sec., for 
a period less than 
10sec.and then gone. 

- Pre-ample that the test discovered an 

object/smoke in the chamber 

- It could have been an object in the chamber, which was 

taken as smoke. 

 

Tekniske spesifikasjoner 500-IDx: 

Type:  

 

500-IDx (x=O, I, T) 

Detector types:: 

 

IDO: Optical,    IDI: Ionical,   IDT: Heat/Temperature 

Certified acc. to: 

 

EN54-7 (500-IDI, 500-IDO), EN54-5 (500-IDT) 

Sensitivity:  

 

Acc. To  EN54-7 (500-IDI og 500-IDO), EN54-5 Class A1 (500-IDT) 

 

 

500-IDT: Alarm at approx. 60

0

C, Rate of Rise 9

0

C/min.  

Power: 

  

9-24VDC, polarity protected 

Current consumption standby: 

 Less than 50 µA  (can change when detector are being tested.) 

Current consumption in alarm:   20 - 25mA   
Siren power: 

 

12-24 VDC. Polarity protected (Input and output is EMC protected.).  

Siren current: 

 

I<10mA. (The circuit is galvanic isolated from detector.) 

Sound siren: 

 

85 dB(A)/3 m .  

Testing:                             

 Test gas – for 500-IDI & 500-IDO. Pre-warning after 4 sec. and a red blink every sec. 
After 10 sec (10 samples) the detector will activate fire alarm and led will have steady red light. 

     

 

Heat (i.e. hair dryer) 500-IDT 

     

 

NB

: The LED is not a push-button, DO NOT push! 

With Diagnostic system  (DS-500) and PC. Test report stored in PC or printed.. 

Memory: 

 

Memory stores the last 32 consecutive events in eeprom. (No Timing.) 

Reset alarm: 

 

Remove power for a short period. (approx. 2 sec.). 

Temp. : 

 

-10 

o

C to +55 

o

Humidity:   

 

95%RH (No condensation) 

Size: 

 

D=118mm, H=36mm, (H=42 mm included base) 

 

Technical spec.   500-Re (relay Base): 

Power: 

 

9-24VDC 

Resistive load: 

 

0,5A v/125Vac, 1A v/30VDC 

Max breaking current: 

 

1A 

Max Power: 

 

125VAC, 48VDC 

Max Breaking Power: 

 

62,5VA, 33W 

Temp: 

 

-10 

o

C to +55 

o

Dimensions: 

 

D=104mm, H=12mm, (build 6mm only when mounted to detector) 

Humidity:   

 

95%RH (No condensation) 