3.6.5 System Setup
System Setup allows the programmer to configure the following control panel features:
•
Trouble Reminder
: This feature, when enabled, provides an audible reminder that
an alarm or trouble still exists on the FACP after the control panel has been
silenced. The control panel piezo sounder will pulse once every 15 seconds
during an alarm and every two minutes during a trouble condition, after the
Alarm Silence or Acknowledge key is pressed. The piezo will continue to sound
at these rates until the alarm or trouble condition is cleared. If the trouble
condition is not cleared within 24 hours, the panel will reactivate the trouble
sounder and retransmit the trouble condition to the central station if connected.
•
Banner:
This option allows the user to change the top two lines of the LCD
display from the factory default readout of
FIRE-LITE ALARMS INC
to a user
defined readout when the control panel is in Normal condition.
•
Time-Date:
This feature allows the programmer to set the time, display format
(24 hr or 12 hr), date and daylight savings time feature into the FACP memory
•
Timers:
This option allows the programmer to set the PAS (Positive Alarm
Sequence) time delay, Pre-Signal time delay and Waterflow time delay.
•
NACs:
This feature allows the programmer to configure the control panel
Notification Appliance Circuits for a variety of options, such as circuit type,
silenceable/nonsilenceable, autosilence, coding, silence inhibit, zone assignment
and enable/disable.
•
Relays:
This option allows programming of two onboard relays for activation by
various control panel events, such as alarm, trouble, supervisory, etc.
•
Canadian Option:
This option allows the automatic programming of ionization
smoke detector sensitivity thresholds to Canadian specifications.
•
Waterflow Silenceable:
This option provides the ability to silence any output
circuit activated by a monitor module programmed as a waterflow type.
Pressing
2
for System Setup, while viewing Programming Screen #2, will cause the
following screens to be displayed:
PROGRAMMING
1=LOOP SETUP
2=SYSTEM SETUP
3=VERIFY LOOP
Programming Screen #2
SYSTEM SETUP
1=TROUBLE REM OFF
2=BANNER
3=TIME-DATE
System Setup Screen #1
SYSTEM SETUP
1=TIMERS
2=NAC
3=RELAYS
System Setup Screen #2
SYSTEM SETUP
1=CANADIAN OPT. OFF
2=WATERFLOW SIL. NO
System Setup Screen #3