,QVWDOODWLRQ
0RXQWLQJ7UDQVIRUPHU
068'31$
2.2 Mounting Transformer
One XRM-24(E) transformer is supplied standard with the control panel. An optional
second XRM-24(E) transformer can be ordered and installed to provide maximum
system power. Install the transformers in the locations indicated in the following
illustration.
1. Mount the Standard XRM-24 Transformer in the lower transformer mounting
location by positioning the wiring connector to the right as illustrated in the
following figure.
2. Slide the bottom transformer mounting bracket into the embossed mounting
pocket as illustrated.
3. Secure the top transformer mounting bracket to the mounting stud with the
supplied screw.
4. If the optional second XRM-24 Transformer is being installed, mount it in the
upper transformer mounting location by positioning the wiring connector to the
right as illustrated in the following figure.
5. Slide the top transformer mounting bracket into the embossed mounting pocket
as illustrated.
6. Secure the bottom transformer mounting bracket to the mounting stud with the
supplied screw.
7. Connect the Standard XRM-24 Transformer plug to Transformer 1 Connector
J10 on the FACP main circuit board
8. Connect the Optional XRM-24 Transformer plug to Transformer 2 Connector J11
on the FACP main circuit board.
9. Complete the installation as detailed in the following sections.
Figure 2.2 Transformer Mounting
Standard XRM-24 Transformer
Optional XRM-24 Transformer
Mounting Pocket
Mounting Pocket
Mounting Studs
Summary of Contents for MS-9200UD