Product Description
Components
18
MS-9200UD PN 51906:A 12/10/02
1.6 Components
Main Circuit Board
The main circuit board contains the system’s CPU, power supply, other primary
components and wiring interface connectors. The 4XTMF option module plugs in and
is mounted to the main circuit board. The circuit board is delivered in the MS-9200UD
kit and must be mounted to the backbox (refer to circuit board illustration on page 10).
Cabinet
The MS-9200UD cabinet is red with a navy blue front overlay.
The backbox provides space for two batteries (up to 18 Amp
Hour). Ample knockouts are provided for system wiring. Also
available is an optional dress panel, which mounts to the inside
of the cabinet (required by ULC for Canadian installations).
The dress panel must be installed to meet FM requirements.
Transformer Assembly
One 100VA transformer is provided standard
with the panel (3.6 amps maximum). An
optional 100 VA transformer XRM-24
(XRM-24E for the MS-9200UDE) is available
to provide maximum system and accessory
power (6.6 amp total).
Batteries
The MS-9200UD cabinet provides space for
two batteries (up to 18 Amp Hour). Batteries
larger than 18 Amp Hour require an external
charger such as the CHG-75 or CHG-120F
and a UL listed battery box such as the BB-
55F. Batteries must be ordered separately.
1.6.1 Intelligent Addressable Detectors: Newer Series
Intelligent, addressable detectors provide information to the control panel on an SLC
Signaling Line Circuit (refer to the SLC Wiring Manual for detailed information on
device installation, wiring and operation). This allows the control panel to continually
process the information to determine the status (alarm, trouble, maintenance or normal)
of each detector. Each detector responds to an SLC address that is set in the detector
head using built-in rotary decimal switches. Note that a blinking LED on an intelligent
detector indicates communication between the detector and the control panel. Refer to
the Fire•Lite Device Compatibility Document for a list of approved detectors.
Smoke Detectors (Photoelectric)
The SD350 is an intelligent, addressable low profile photoelectric smoke detector
which provides smoke sensing technology. The SD350T includes a 135
o
fixed thermal
sensor.
Smoke Detector (Ionization)
The CP350 is an intelligent, addressable low profile ionization smoke detector which
measures the level of combustion products in its chamber using the ‘ionization
principle.’
See Page
ms9200UD.cdr
Standard
XRM-24(E)
Optional
XRM-24(E)
9200xf
or
.c
dr
-
-
+
+
Battery Cable P/N 75287
9200batt.cdr
Summary of Contents for MS-9200UD
Page 4: ...4 MS 9200UD PN 51906 A 12 10 02 Notes ...
Page 180: ...180 MS 9200UD PN 51906 A 12 10 02 Notes ...
Page 188: ... 06 8 31 Notes ...
Page 189: ...06 8 31 Notes ...
Page 190: ... 06 8 31 Notes ...