Operating Instructions
Read Status
142
MS-9200UD PN 51906:A 12/10/02
4.22.1 System Point
Pressing
1
while viewing Read Status Screen #1 will cause the following screen to be
displayed:
The operator selects the type of device which is to be viewed by pressing
1
for Detector
or
2
for Module. If
1
is pressed, the display will change to the following screen:
Entering the three digit detector address will cause the control panel to display the
current status of the selected device. For example, if a detector with address
001
on the
SLC loop is entered, a display similar to the following will appear:
The information in the preceding display includes:
•
NORMAL
- the present status (could also be ALARM, TROUBL, DISABL, etc.)
•
SMOKE (PHOTO)
- the device type which is a photoelectric smoke detector
(could also be ION for ionization smoke detector)
•
NORTH CLASSROOM
- the Adjective/Noun label for this device
•
Z005
- the first of five possible assigned software zones
•
1D001
-
1
= SLC Loop,
D
= Detector,
001
= Address 001
• V - Alarm Verification Enabled (V = Yes, * = No)
• S - Silenceable for control modules (S = Yes, * = No)
• W - Walktestable for control and monitor modules (W = Yes, * = No)
READ STATUS
1=SYSTEM POINT
2=ZONES
3=POWER
Read Status Screen #1
READ SYSTEM POINT
SELECT TYPE
1=DETECTOR
2=MODULE
READ SYSTEM POINT
ENTER DETECTOR#
***
NORMAL SMOKE(PHOTO)
NORTH CLASSROOM
Z005
V 1D001