Operating Instructions
Read Status
144
MS-9200UD PN 51906:A 12/10/02
4.22.3 Power
Pressing
3
while viewing Read Status Screen #1 will cause the following screens to be
displayed:
A real-time display of the control panel voltages can be used to determine if a problem
exists in the system.
Note that
Power Screen #3
will only be displayed if the NACKEY
NAC option card is installed, in JP8 of the main circuit board, for Class B operation.
The following table lists the circuit being measured, possible conditions and their
respective voltage ranges:
Circuit
Condition
Voltage Range
Battery
Normal Battery (nominal)
27.05 to 28.15 VDC
Low Battery
20.0 to 20.8 VDC
No Battery
0 to 18.36 VDC
24V Resettable
Normal
21.25 to 27.50 VDC
24V Nonresettable
Normal
21.25 to 27.50 VDC
Charger
Normal
21.87 to 29.84 VDC
NAC 1 or NAC 2
Normal
-1.3 to -1.6 VDC
Open Circuit
-2.3 to -2.5 VDC
Short Circuit
0 to 1.0 VDC
POWER
BATTERY 27.21V
24 V RST 25.31
Power Screen #1
POWER
CHARGER 28.36V
NAC 1 -1.49V
NAC 2 -1.49V
Power Screen #2
POWER
NAC 3 -1.49V
NAC 4 -1.49V
Power Screen #3