Programming
Master Programming Level
108
MS-9200UD PN 51906:A 12/10/02
The Communication Format is determined by the type of receiver that the DACT is
transmitting to.
Consult your Central Station for proper selection or consult our
factory representatives. For any format chosen, the control panel automatically
programs all of the event codes.
Select the Communication Format by pressing the corresponding number key while
viewing the appropriate Comm Format screen. The following table describes each
format:
Event Codes
Pressing
1
while viewing Primary/Secondary Screen #4 will cause the following
screen to be displayed:
Pressing the down arrow key allows viewing of all Events associated with the
selected Communication Format. Pressing the number corresponding to the event
displayed in each screen will display its default event code which can be customized
by the programmer. For example, pressing
1
for Pull Station will display the
following screen which allows the Event Code to be changed from the default
value.
The tables on the following pages list all of the Events and their default Event
Codes for the various Communication Formats.
Table 3.1 Communication Formats
Screen Selection
Communication Format Description
ADEMCO EXPRESS 4P1
4+1 Ademco Express Standard, DTMF, 1400/2300 ACK
ADEMCO EXPRESS 4P2
4+2 Ademco Express Standard, DTMF, 1400/2300 ACK
3P1S C18 A23
3+1 Standard 1800 Hz Carrier, 2300 Hz ACK
3P1E C18 A23
3+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
3P1S C19 A14
3+1 Standard 1900 Hz Carrier, 1400 Hz ACK
3P1E C19 A14
3+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
4P1S C18 A23
4+1 Standard 1800 Hz Carrier, 2300 Hz ACK
4P1E C18 A23
4+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
4P1S C19 A14
4+1 Standard 1900 Hz Carrier, 1400 Hz ACK
4P1E C19 A14
4+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
4P2S C18 A23
4+2 Standard 1800 Hz Carrier, 2300 Hz ACK
4P2E C18 A23
4+2 Expanded 1800 Hz Carrier, 2300 Hz ACK
4P2S C19 A14
4+2 Standard 1900 Hz Carrier, 1400 Hz ACK
4P2E C19 A14
4+2 Expanded 1900 Hz Carrier, 1400 Hz ACK
ADEMCO CONTACT ID
Contact ID, DTMF, 1400/2300 ACK
CENTRAL STATION
1=EVENT CODES
Primary/Secondary Screen #4
EVENT CODES
1=PULL STATION
2=MON-USER-DEF-1