Transmittal Priorities
Central Station Communications
MS-9200UD PN 51906:A 12/10/02
157
5.1 Transmittal Priorities
The integral communicator transmits highest priority events first. Events, in terms of
priority, are listed below in descending order:
1. Alarms (highest priority level)
✓
Pull stations
✓
Waterflow
✓
Smoke detector
✓
Other alarm types
2. Supervisory Zone
3. System Troubles
✓
Zone disabled
✓
Fire drill
✓
AC fail (after delay)
✓
Zonal faults
✓
Earth fault
✓
Low battery
✓
Telephone line fault
✓
Notification Appliance Circuits fault
✓
Communication trouble
✓
Annunciator trouble
✓
System off normal
4. Restoral Reports
✓
Zone alarm
✓
Supervisory
✓
Zone(s) enabled
✓
Fire drill
✓
AC
✓
Zone fault
✓
Earth
✓
Battery
✓
Telephone line
✓
Notification Appliance Circuits
✓
Communication
✓
Annunciator trouble
✓
System off normal
5. 24 Hour Test (lowest priority)
Red LEDs are provided on the circuit board to identify which telephone line is
activated. Also, a green LED labeled
Kissoff
will turn on whenever the control panel
has successfully transmitted reports to the Central Station. The
Kissoff
LED may turn
on several times during communications with a Central Station.