![Fimer PVS-100-TL B2 Product Manual Download Page 51](http://html.mh-extra.com/html/fimer/pvs-100-tl-b2/pvs-100-tl-b2_product-manual_2289268051.webp)
EN
51
5.2.3 Distances
• Maintenance operations entails removing the front cover. Always
observe the required installation safety distances in order to allow
routine check and maintenance operations.
• Provide a sufficient working space in front of the inverter that
allows to open the front covers
(07)(54)
and to allows wiring
connections on the wiring box.
• Install at a height which takes into consideration the weight of
the unit and in a position which is suitable for servicing, unless
suitable means will be provided to carry out these mentioned
operations.
• If possible, install at eye-level so to allow to easily check the
status LEDs
(08)
.
• Respect the minimum distances from surrounding objects that
could prevent the inverter installation and restrict or block the air
flow.
50cm
*100cm
(*) minimum free space to operate with the inverter
ATTENTION –
A
Do not install any object (e.g. AC or DC
cables) that could be damaged by overheating from outgoing
hot air flow coming from side fan sections (ΔT= +15 °C
compared to ambient temperature). In case of this kind
of installation needs, please evaluate the installation of a
proper air deflector. Always respect the minimum distances
required.
A
B
C
C
D
The minimum clearance distances depends from multiple factor:
1. Ventilation flow on the rear side of the inverter.
Depending of the support where the inverter is installed it changes
the upper (A) required free space: if the inverter is installed on a
support without any openings (e.g. a wall), the heat flow will be
entirely directed to the top of the inverter; for this reason the upper
(A) minimum required free space must be 50 cm.
Otherwise in case of the inverter is installed on a support with
openings (e.g. frame installation) the heat can freely flow on the
rear side of the inverter; so the upper (A) minimum required free
space can be reduced to 15 cm.
15
cm
50
cm
2. Possible flooding or damage during grass cutting operation.
It changes the bottom
(B)
or the rear (
(D)
- only in case of horizontal
installation) required free space: If the inverter is installed in a
place where there are concrete risk of flooding or grass cutting
evenience, the bottom
(B)
or the rear (
(D)
- only in case of
horizontal installation) minimum recommended free space is 50
cm; otherwise in case of the inverter is installed in a place where
there aren’t risk of flooding or grass cutting evenience, the bottom
(B)
and rear (
(D)
- only for horizontal installation) minimum required
free space must be 15 cm.
15
cm
50
cm
50
cm
15
cm
50
cm
50
cm