EN
24
PVS-100
Wiring Box version
Standard, S2
User Interface
4 LEDs, Web User Interface
Communication protocol
Modbus RTU/TCP (Sunspec compliant)
Commissioning tool
Web User Interface, Mobile APP/APP for plant level
Remote monitoring services
Aurora Vision® monitoring portal
Advanced features
Embedded logging, direct telemetry data transferring to FIMER cloud
Environmental
Operating ambient temperature range
-25...+60°C/-13...140°F with derating above 40°C/ 104°F
Storage temperature
-40°C...+85°C / -40°F...185°F
Relative Humidity
4…100 % with condensation
Sound pressure level, typical
68dB(A)@ 1m
Maximum operating altitude without derating
2000 m / 6560 ft
Environmental pollution degree
classification for external environments
3
Environmental class
Outdoor
Climatic category according to IEC 60721-3-4
4K4H
Physical
Environmental Protection Rating
IP 66 (IP54 for the cooling section)
Cooling System
Forced air
Dimensions (H x W x D)
869x1086x419 mm / 34.2” x 42.7” x 16.5”
Weight
70kg / 154 lbs for power module ; ~55kg / 121 lbs for wiring box;
Overall max 125 kg / 276 lbs
Mounting system
Mounting bracket vertical & horizontal support
Overvoltage rating as per IEC 62109-1
II (DC input) III (AC output)
Safety
Safety class
I
Insulation Level
Transformerless
Marking
CE
(8)
Safety, EMC and Radio Spectrum Standards
IEC/EN 62109-1, IEC/EN 62109-2, EN 61000-6-2,
EN 61000-6-4, EN55011:2017
Grid standard
(check the availability with your sales channel)
CEI 0-16, CEI 0-21, IEC 61727, IEC 62116, IEC 60068, IEC
61683, JORDAN IRR-DCC-MV, DRRG/DEWA,
Chile LV/MV, BDEW, Belg C10-C11, EN50438 GIreland,
EN50549-1/2, CLC-TS50549-1/2, AS/
NZS4777.2, UK G59/3, EREC G99-1, MEA, PEA, ISO-IEC Guide
67 (system 5), NRS 097-2-1, P.O. 12.3,
ITC-BT-40, UNE 206006 IN, VDE-AR-N 4105, VDE-AR-N 4110,
VDE-AR-N 4120, VDE V 0-126-1-1, VFR
2019, UTE C15-712-1, Taiwan
Accessories
Assembly accessories
PVS Installation Kit
AC Plate, Single Core Cables
Plate with 5 individual AC cable glands: 4 x M40: Ø 19...28mm, 1
x M25: Ø 10...17mm
AC Plate, Multi Core Cables
Plate with 2 individual AC cable glands: 1 x M63: Ø 37…53mm, 1
x M25: Ø 10...17mm
PVS-100/120 PRE-CHARGE BOARD KIT
Allow the monitoring of the inverter when DC source is not
available and night time operation with restart capability
PVS-100/120 GROUNDING KIT
(9)
Allow to connect the negative input pole to ground
(7)
1. Maximum number of opening 5 under overloading
4. The AC voltage range may vary depending on specific country grid standard
5. Frequency range may vary depending on specific country grid standard
6. In the event of a fault, limited by the external protection envisaged on the AC circuit
7. Only in IT-system (an AC SPD reconfiguration is needed)
8. Hereby, Power-One Italy S.p.A. (A Member of the FIMER Group) declares that the radio equipments (radio module combined with
the inverter), to which this user manual refers, are in compliance with the Directive 2014/53/EU. The full text of the EU Declaration of
Conformity is available at the following internet address:
9. When PVS-100/120 GROUNDING KIT is installed, Residual Current Monitoring do not fully operate. Inverter must be installed and
operate in “restricted areas (access limited to qualified personnel)” according to IEC 62109-2
Features not specifically mentioned in this data sheet are not included in the product.