P/N
06
‐
791
‐
4
(Rev.
4)
Page
23
704
SW
10
th
Street,
P.O.
Box
610,
Blue
Springs,
Missouri
64013
‐
0610
U.S.A.
●
Phone:
(816)
229
‐
3405
●
www.fike.com
2.7.
Check
Valve
The
ARGCO
Check
Valve
is
used
in
a
DuraQuench
system
to
prevent
the
reversal
of
water
flow.
In
the
fully
‐
open
position
the
clapper
is
held
tightly
against
the
valve
body,
out
of
the
flow
stream,
to
provide
maximum
fl
ow
area
and
prevention
of
clapper
fl
utter.
The
clapper
design
produces
quick,
non
‐
slam
closure
before
flow
reversal
can
occur
while
meeting
FM
requirements
for
anti
‐
water
hammer
valve
rating.
Each
valve
is
hydrostatically
tested
for
leak
tightness
to
500
PSI.
Specifications
Part
Number
02
‐
14915
‐
1
(2”)
02
‐
14915
‐
2
(2
1/2”)
02
‐
14915
‐
3
(3”)
Working
Pressure
300
psi
(20.7
bar)
Maximum
Test
Pressure
500
psi
(34.5
bar)
Working
Temperature
250°F
(120°C)
maximum
Weight
8
lbs.
(3.63
kg)(2”
&
2
1/2”)
11
lbs.
(4.99
kg)(3”)
End
Connection
Grooved
(Both
Ends)
MATERIALS:
Body
Ductile
Iron
(ASTM
A
‐
536)
Epoxy
Coated
Color
Red
Clapper
304
Stainless
Steel
(ASTM
A167)
Clapper
Facing
Grade
EPDM
Temperature
Range
‐
40°
to
230°F
Seat
Ring
304
Stainless
Steel
(ASTM
A123)
Housing
Stainless
Steel
316L
Coating
NiSn
Strainer
Stainless
Steel
316L
Spring
302
Stainless
Steel
(ASTM
A313)
Hinge
Pin
302
Stainless
Steel
(ASTM
A580)
Hinge
Pin
Bushings
Sintered
Bronze
(ASTM
B438)
Hinge
and
Drain
Plugs
Cast
Iron
(ASTM
A126)
Class
A
Listing
/
Approval
FM
Approved
Figure
17:
Check
Valve
Summary of Contents for DuraQuench
Page 93: ......