P/N
06
‐
791
‐
4
(Rev.
4)
Page
19
704
SW
10
th
Street,
P.O.
Box
610,
Blue
Springs,
Missouri
64013
‐
0610
U.S.A.
●
Phone:
(816)
229
‐
3405
●
www.fike.com
Motor
and
Pump
Specifications
Skid
P/N
02
‐
14909
‐
1
‐
X
‐
X
02
‐
14909
‐
2
‐
X
‐
X
02
‐
14909
‐
3
‐
X
‐
X
02
‐
14909
‐
4
‐
X
‐
X
02
‐
14909
‐
5
‐
X
‐
X
02
‐
15270
(Jockey)
3
‐
Phase
AC
Standard
Motors
Motor
Type
BALDOR
BALDOR
BALDOR
BALDOR
BALDOR
ML80CA
Rated
Power
–
P2
7.5
kW
(10
HP)
11
kW
(15
HP)
18.5
kW
(25
HP)
11
kW
(15
HP)
18.7
kW
(25
HP)
1.12
kW
(1.5
HP)
Mains
Frequency
60Hz
60Hz
60Hz
50Hz
50Hz
50/60Hz
Rated
Voltage
(V)
3
x
208
‐
230/460*
3
x
208
‐
230/460*
3
x
230/460*
3
x
380
‐
415*
3
x
200/400
3
x
220
‐
240/
380
‐
415
(50Hz)
3
x
220
‐
255/
380
‐
440
(60Hz)
Rated
Current
(A)
24.8
‐
23.8/11.9
38
‐
35/17.5
56/28
20.2
‐
18.6
64/32
4.35/2.50
(50Hz)
4.15
‐
4.00/
2.40
‐
2.30
(60Hz)
Rated
Speed
(rpm)
3525
3520
3530
2930
2920
2840
‐
2870
(50Hz)
3420
‐
3470
(60Hz)
Motor
Locked
‐
Rotor
Code
(KVA/HP)**
K
(8.0
‐
8.99)
G
(5.6
‐
6.29)
J
(7.1
‐
7.99)
H
(6.3
‐
7.09)
H
(6.3
‐
7.09)
A
(0
‐
3.14)
Grundfos
Pumps
Type
CRN10
‐
12
CRN10
‐
14
CRN20
‐
10
CRN15
‐
12
CRN32
‐
10
CR1S
‐
17
Pump
Speed****
3,470
rpm
3,470
rpm
3,521
rpm
2,924
rpm
2,934
rpm
3,463
rpm
Rated
Flow
(duty
point)
53.27
gpm
(201.6
lpm)
53.27
gpm
(201.6
lpm)
111.39
gpm
(421.70
lpm)
74.85
gpm
(283.3
lpm)
132.09
gpm
(500
lpm)
4.8
gpm
(18.3
lpm)
Rated
Head
446.5
ft.
(136
m)
512.5
ft.
(156
m)
561.4
ft.
(171
m)
444.9
ft.
(136
m)
500.3
ft.
(152.5
m)
318
ft.
(97
m)
Maximum
Head
577.4
ft.
(176
m)
669.3
ft.
(204
m)
698.8
ft.
(213
m)
554.5
ft.
(169
m)
638.5
ft.
(194.6
m)
478.7
ft.
(145.7
m)
Maximum
Ambient
Temperature
140°F
(60°C)
104°F
(40°C)
104°F
(40°C)
104°F
(40°C)
104°F
(40°C)
140°F
(60°C)
Maximum
Pressure
at
Stated
Temp
363
psi
/
248°F
(25
bar
/
120°C)
363
psi
/
248°F
(25
bar
/
120°C)
363
psi
/
248°F
(25
bar
/
120°C)
363
psi
/
194°F
(25
bar
/
90°C)
435
psi
/
194°F
(30
bar
/
90°C)
232
psi
/
248°F
(16
bar
/
120°C)
Maximum
Inlet
Pressure***
100
psi
(6.9
bar)
100
psi
(6.9
bar)
100
psi
(6.9
bar)
100
psi
(6.9
bar)
100
psi
(6.9
bar)
100
psi
(6.9
bar)
Liquid
Temp.
Range
‐
4
to
+248
°F
(
‐
20
to
+120
°C)
‐
4
to
+248
°F
(
‐
20
to
+120
°C)
‐
4
to
+248
°F
(
‐
20
to
+120
°C)
‐
4
to
+194
°F
(
‐
20
to
+90
°C)
‐
4
to
+248
°F
(
‐
20
to
+120
°C)
‐
4
to
+248
°F
(
‐
20
to
+120
°C)
*Usable
at
208
Volts.
**The
motor’s
inrush
current,
also
known
as
locked
‐
rotor
amps
or
LRA,
can
be
calculated
by
inserting
the
KVA/HP
value
into
the
following
formula:
LRA
=
KVA/HP
x
Motor
HP
x
1000
/
1.732
x
Motor
Voltage
***Current
inlet
pressure
+
churn
(no
flow)
pressure
must
always
be
lower
than
the
maximum
permissible
system
operating
pressure
to
prevent
potential
damage
to
the
bearing
in
the
motor
or
reduced
life
of
the
shaft
seal.
****Pump
speed
on
which
data
is
based.
Summary of Contents for DuraQuench
Page 93: ......