P/N
06
‐
791
‐
4
(Rev.
4)
Page
53
704
SW
10
th
Street,
P.O.
Box
610,
Blue
Springs,
Missouri
64013
‐
0610
U.S.A.
●
Phone:
(816)
229
‐
3405
●
www.fike.com
Test
Header
Connection
The
test
header
piping
and
components
must
be
field
installed
in
accordance
with
the
manufacturer’s
requirements
and
as
shown
on
the
system
design
documents.
In
order
to
prevent
water
damage,
the
discharge
from
the
test
header
connection
shall
be
piped
to
a
safe
discharge
location
where
there
is
adequate
drainage
for
the
pressurized
water
discharge.
A
flanged
outlet
and
an
isolation
valve
are
provided
on
the
DuraQuench
pump
skid
to
allow
easy
connection
and
isolation
of
the
test
header
components.
See
Figure
46.
Figure
46:
Test
Header
Connection
1.
Suction
flange
9.
Discharge
Pressure
Gauge
2.
Suction
basket
strainer
10.
Discharge
isolation
valve
(monitored)
3.
Suction
pressure
gauge
11.
Discharge
flange
4.
Circulation
relief
valve
(opens
at
275
psi/19
bar)
12.
Flow
meter
(optional)
5.
Centrifugal
pump
and
motor
13.
Isolation
valve
6.
Pressure
relief
valve
(opens
at
245
psi/16.9
bar)
14.
Drain
valve
7.
Test
header
stop
valve
(monitored)
15.
Test
header
connection
8.
Test
header
flange