Item
Description
Function
6
Discharge
Pressure
Gauge
Indicates
pressure
of
the
water
supply
being
generated
by
the
pump
at
its
outlet.
7
Discharge
Isolation
Valve
(butterfly)
Allows
the
water
supply
to
the
system
piping
network
to
be
turned
off
for
service
or
maintenance
of
the
pump
skid
unit.
Valve
is
monitored
by
the
releasing
control
panel
and
provides
an
alarm
signal
when
the
valve
is
not
in
the
fully
open
position.
8
Discharge
Pipe
Connection
Pipe
flange
allows
easy
connection
of
system
distribution
piping.
See
System
Piping
Connections
for
flange
size.
9
Recirculation
Loop
Provides
a
path
for
continuous
water
flow
through
the
pump
when
the
pump
is
operating
in
churn
(no
flow)
condition.
10
Relief
Valve
Allows
the
diversion
of
water
through
the
recirculation
loop
to
limit
excess
pressure
in
the
system.
11
Test
Header
Isolation
Valve
(butterfly)
Allows
the
water
supply
from
the
fire
pump
to
be
routed
to
a
connected
test
header
for
the
purpose
of
measuring
the
system
flow
rate
during
acceptance
testing
and
during
annual
testing.
12
Test
Header
Pipe
Connection
Pipe
flange
allows
easy
connection
of
test
header
piping
to
the
pump
skid.
See
System
Piping
Connections
for
flange
sizes.
13
Pump
Controller
Provides
a
means
to
start
the
fire
pump
automatically
or
manually
in
response
to
a
fire
event.
Provides
remote
alarm
connections
for
fire
pump
monitoring
(i.e.,
pump
running,
AC
power
failure,
phase
reversal,
etc.).
Controller
can
be
activated
via
a
normally
closed
remote
contact
from
a
releasing
control
panel
(deluge
system)
or
via
a
pressure
sensing
line
connection
(wet
pipe
system).
14
Motor
Bracing
Strap
Provides
bracing
of
pump
motor.
Pump
Skid
with
Pressure
Maintenance
Pump
Components
For
installations
where
a
jockey
pump
is
required,
a
pressure
maintenance
(jockey
or
make
‐
up)
pump
kit
(P/N
02
‐
15270)
can
be
ordered
from
Fike.
The
kit
includes
a
jockey
pump
controller
dual
rated
for
50/60
Hz
and
a
3.5
GPM
centrifugal
pump
coupled
to
a
50/60
Hz
motor.
If
initially
ordered
as
part
of
the
pump
skid,
the
jockey
pump
and
required
check
and
isolation
valves
will
be
factory
mounted
onto
the
DuraQuench
pump
skid,
as
shown
in
Figure
13.
The
jockey
pump
controller
(included
with
the
kit)
must
be
mounted
off
the
pump
skid.
The
pressure
sensing
line
and
pump
motor
control
wiring
connections
form
the
jockey
pump
to
the
jockey
pump
contller
must
be
filed
installed
in
accordance
with
the
requiremnts
of
NFPA
20.
NOTE
‐
DuraQuench
systems
configured
with
a
pressure
maintenance
pump
are
not
within
the
scope
of
the
DuraQuench
FM
approval.
Figure
13:
Pump
Skid
Configuration
with
Factory
Installed
Jockey
Pump