Figure
51:
OH
‐
VSO
Typical
Nozzle
Mounting
Figure
52:
Spanner
Wrench
4.6.
Signage
Install
permanently
marked,
weatherproof,
metal
or
rigid
plastic
identification
signs
at
all
control,
drain,
and
test
connection
valves.
The
signs
shall
be
secured
with
corrosion
resistant
wire,
chain,
or
other
approved
means.
A
system
design
information
sign
shall
be
attached
to
the
pump
skid
and
shall
include
the
following
information:
1.
Location
of
the
design
area
or
areas
2.
Design
area
of
water
application
or
volume
of
space
protected.
3.
Nozzle
manufacturer
and
model
number
4.
Area
per
nozzle
5.
Total
number
of
nozzles
in
design
area
6.
Minimum
rate
of
water
application
(density)
7.
Total
water
requirement
as
calculated
8.
Description
of
hazard
protected
9.
Description
of
any
compartment
or
enclosure
characteristics
that
are
essential
to
system
performance
10.
Name
of
installing
contractor
and
contact
information