APPENDIX A
UL S2203
CyberCat 254/1016 Installation Manual
A-3
FM
P/N: 06-326
Rev 14, 09/2015
Section 3 – Auxiliary Power (CSC + SPS)
Item
Device Description
Standby
Current per
Unit (Amps)
Qty
Total
Standby
Current per
item (Amps)
Alarm
Current per
Unit (Amps)
Qty
Total Alarm
Current per
item (Amps)
1
68-140 FAAST
0.500
x
=
0.650
x
=
2
68-302 FAAST XT
0.500
x
=
0.650
x
=
3
55-042/047 SCM w/ Solenoid
[Note 2]
NA
x
NA
=
NA
x
=
4
10-2413 Master-box Supervisor
0.022
x
=
0.283
x
=
4a
Master-box Trip Coil
[Note 2]
NA
x
NA
=
NA
x
=
5
55-055/060 CZM
NA
x
NA
=
NA
0.090
x
=
6
63-1064 Sounder Base
0.007
x
=
0.027
x
=
7
10-2528/-2476 DACT
0.150
x
=
0.190
x
=
8
10-2630 2-button RDU
0.036
x
=
0.139
x
=
9
10-2631 10-button RDU
0.036
x
=
0.139
x
=
10
10-2646 14-button RDU
0.036
x
=
0.139
x
=
11
10-2627 Ethernet Module
0.097
x
=
0.134
x
=
12
10-2583 Multi-Interface
0.200
x
=
0.200
x
=
13
10-2411 LED Graphic Micro
0.067
x
=
0.140
x
=
14
10-2663 Smoke Control Module
0.058
x
=
0.112
x
=
15
10-2667 20-Zone Remote Annun.
0.051
x
=
0.148
x
=
16
10-2658 6-Zone Smoke Control
0.048
x
=
0.102
x
=
17
10-2659 I/O Switch Card
0.051
x
=
0.140
x
=
18
10-2660 20-Zone Annun. Card
0.051
x
=
0.144
x
=
19
10-2661 Audio Ctrl Switch Card
0.048
x
=
0.102
x
=
20
10-2728 Fire-Phone Switch Card
0.053
x
=
0.075
x
=
21
10-2730 Supp. Fire-Phone Card
(Max. 4)
0.018
x
=
0.038
x
=
22
24-135 Fire-Phone Ctrl Module
0.018
x
=
0.008
x
=
23
10-2777 Relay Assy.
[Note 3]
0.047
x
=
0.109
x
=
24
10-2204 CRM4 Relay
[Note 4]
0.011
x
=
0.040
x
=
25
10-2770 HPM4 Relay
[Note 4]
NA
x
NA
=
NA
0.086
x
=
26
10-2785 Relay Card
[Note 4]
0.032
x
=
0.256
x
=
27
10-2792 Class A Peripheral Card
0.057
x
=
0.057
x
=
28
10-2751 FCC Digital Paging Assy
0.103
x
=
0.140
x
=
29
10-2814 LOC Digital Paging Assy
0.103
x
=
0.140
x
=
30
10-2616 Keltron Printer
0.200
x
=
1.200
x
=
31
10-2277 VESDA HLI
0.245
x
=
0.245
x
=
Total Aux. Power Standby
Current (Amps):
Total Aux. Power
Alarm Current (Amps):
Insert totals in Section 1 – Line Item 9
Section 3 Notes:
1.
Include current draw of devices in this section only if 24vdc power is supplied by the CyberCat system controller or the
supplemental power supply.
2.
Indicate alarm current draw of the coil that is connected to the module.
3.
Assembly includes control card and relay bus card. Add the quantity of CRM4 and HPM4 relay cards installed on the bus card
in rows 24 and 25.
4.
Current values shown assume all relays are active.