3.0 SYSTEM COMPONENTS
UL S2203
CyberCat 254/1016 Installation Manual
3-5
FM
P/N: 06-326
Rev 14, 09/2015
Exhibit 3-6: CyberCat Controller Terminal Specifications – Cont.
Terminal
Block
Terminal
Labels
Function and Electrical
Ratings/Requirements
Wiring Requirements
P4
VESDA
•
RS232 port, power limited and supervised
•
VESDA High Level Interface (HLI) P/N
68-023 connection point
•
Intelligently links Xtralis VESDA detectors
to the CyberCat by zone #, 0 – 255.
Does not require SLC address
68-023 includes 14 ft. (4.27m) RS232 cable
P/N 02-3053 for connection to the CyberCat
controller P4
HLI must be powered from the CyberCat
auxiliary power outputs or a ground fault
condition could occur
P5
Peripherals
(232)
•
RS232 port, power limited and supervised
•
Interface point for Fike Guard voice
evacuation system
•
C-Linx connection point for programming
RS485 peripheral devices
Fike Guard voice evacuation system must
be installed in same room as the CyberCat
panel within 50 ft. (15m) maximum
P6
DACT
(+ -)
•
Power limited and supervised
•
Interface point for Digital Alarm
Communicator Transmitter (Point ID
communication)
•
DACT can be mounted inside the panel
or external in a separate enclosure
Terminal blocks accept 12 – 24 AWG
Peripherals
(485)
(shld,+ , -)
•
Power limited and supervised
•
Connects to RS485 peripheral devices
•
31 peripheral devices maximum
•
Typical circuit voltage will vary between 0
– 1 VDC. It should never be a constant
voltage or 0 VDC
•
Peripheral devices must be configured as
supervised if 2-way communication is
required
RS485 wiring: Belden 9841 or equal. Use
Belden 82841, 82842, or 89841 for plenum
applications
Maximum wire length of 4000 ft. (1219m),
9600 bps, 5 VDC, 1mA
Maximum wire impedance 110
Ω
Maximum wire capacitance 0.05uF
100
Ω termination resistor is required on the
last device on circuit, P/N 02-2519 (supplied
with each device)
T-tapping of circuit is NOT allowed
Terminal blocks accept 12 – 24 AWG
P7
Resettable
Aux Out (+, -,
shld)
•
Power limited and supervised
•
Regulated auxiliary power output rated 24
VDC @ 2A maximum, regulated 28 volts
maximum
•
Fused by F3 for short circuit, 4A field
replaceable fuse, P/N 02-11412
•
Turns off momentarily during system
reset
•
Used to power detectors requiring 24
VDC for operation
The CyberCat controller has a total power
capability of 6 amps. The CyberCat 1016 is
expandable to 12 amps with the addition of
the 10-2474, Supplemental Power Supply
Terminal blocks accept 12 – 24 AWG
Auxiliary
Outputs
(+, -, shld)
•
Power limited and supervised
•
Continuous, regulated auxiliary power
output rated 24 VDC @ 2A maximum,
regulated 28 volts maximum
•
Fused by F4 and F5 for short circuit, 4A
field replaceable fuse, P/N 02-11412
•
Used to power detectors and peripheral
devices requiring 24 VDC for operation
The CyberCat controller has a total power
capability of 6 amps. The CyberCat 1016 is
expandable to 12 amps with the addition of
the 10-2474, Supplemental Power Supply
Terminal blocks accept 12 – 24 AWG