APPENDIX A
UL S2203
CyberCat 254/1016 Installation Manual
A-1
FM
P/N: 06-326
Rev 14, 09/2015
Power calculations must be completed to determine standby and alarm current loads for the system to ensure
that the system power supply is capable of providing the required quantity of power during normal system
operation and fire alarm conditions. The power requirements cannot exceed the capabilities of the system
power supply. Amp-hour requirements must be calculated as well to determine proper back-up battery size
selection.
The following battery calculation form provides the current draw (standby and alarm) of each compatible
device that can be connected to the system. To calculate the required standby and alarm power, as well as
required back-up battery size for the system, simply list the number of each type of device that will be
connected to the system in the quantity column(s) and perform the required calculations.
BATTERY CALCULATION FORM
Section 1 - System Requirements
Item
Description
Standby
Current
per Unit
(Amps)
Qty
Total
System
Standby
Current
per Unit
(Amps)
Alarm
Current
per Unit
(Amps)
Qty
Total
System
Alarm
Current
per Unit
(Amps)
1
10-2525/-2472 System Controller (CSC)
0.275
x
1
=
0.275
0.275
x
1
=
0.275
2
10-2204 CRM4
[Note 7]
0.011
x
=
0.040
x
=
3
10-2254 Reverse Polarity Module
NA
x
NA
=
NA
0.060
x
=
4
10-2482 RS485 Network Module
0.050
x
=
0.050
x
=
5
10-2624 FO Network Module
0.050
x
=
0.050
x
=
6
10-2473 Supplemental Loop Module
(SLM)
[Note 8]
0.100
x
=
0.100
x
=
7
10-2474 Supplemental Power Supply
(SPS)
[Note 8]
0.040
x
=
0.040
x
=
8
Signaling Line Circuits (CSC + SLM)
x
1
=
x
1
=
Section 2 Totals
9
Auxiliary Power (CSC + SPS)
x
1
=
x
1
=
Section 3 Totals
10
Notification Circuits
[Note 9]
NA
x
NA
=
NA
x
1
=
Section 4 Totals
Total System Standby
Current (Amps):
Total System Alarm
Current (Amps):
[Note 1]
[Note 2]
Max. Quiescent Load (Standby):
hr
Total Alarm Load:
min. x 1/60 =
hr
[Note 3]
[Note 4]
Required
Standby Time
(hr)
Total System
Standby Current
(Amps)
Required
Standby Capacity
(Amp-hr)
Required Alarm
Time (hr)
Total System
Alarm Current
(Amps)
Required Alarm
Capacity (Amp-
hr)
x
=
x
=
Required Standby
Capacity (Amp-hr)
Required Alarm
Capacity (Amp-hr)
Total Required
Capacity (Amp-hr)
Optional Factor of
Safety
Adjusted Battery
Capacity (Amp-hr)
+
=
x
=
[Note 5]
[Note 6]