4.0 INSTALLATION
UL S2203
CyberCat 254/1016 Installation Manual
4-13
FM
P/N: 06-326
Rev 14, 09/2015
4.13 CONNECT AC POWER TO THE CONTROLLER
a
WARNING
AC power connections to the CyberCat Controller must be
made with the main power breaker locked out.
The following general steps shall be used to connect AC power to the controller:
1. Remove the (P1) terminal block from the CyberCat board
2. Connect wiring from the primary transformer to the controller’s AC XFMR terminal (P1) as shown in
Exhibit 4-13, making sure to land wires to correct terminal.
3. If the optional supplemental power supply is present, install wiring from the secondary transformer to
the SPS AC XFMR terminal (P21) as shown in Exhibit 4-13, making sure to observe correct polarity.
4. Do NOT energize the AC power source at this time!
SPS
Exhibit 4-13: AC Power Connections
I
Caution
The transformer input should never be connected
to the battery input. Reversing the AC and
Battery input will damage the controller.