4.0 INSTALLATION
UL S2203
CyberCat 254/1016 Installation Manual
4-9
FM
P/N: 06-326
Rev 14, 09/2015
4.11 INSTALL OPTIONAL MODULES
Several optional modules can be installed onto the CyberCat controller to expand its operational capabilities.
The modules contain static sensitive components; therefore, handle them by the edges only and avoid
touching the integrated components. Keep each module in the protective static bag it was shipped in until
time for installation. Always ground yourself with a proper wrist strap before handling the module(s) to reduce
the risk of damage due to static discharge.
The following terminals are provided on the CyberCat controller, as shown on Exhibit 4-8, to allow connection
of the optional modules:
Terminal
Module
P12
CRM4 Relay Module or Reverse Polarity Module
P13
CRM4 Relay Module or Reverse Polarity Module
P15
Supplemental Loop Module
P16
Supplemental Power Supply
P20
Network Modules (RS485 or Fiber Optic)
All of the optional modules, except the DACT, must be installed prior to installing the CyberCat controller into
the enclosure. Refer to the installation instructions supplied with each module for specific installation
instructions.
Note:
If the optional Internal DACT is installed, terminal P12 is no longer available for use.
Note:
Modules installed in terminals P13 and P20 share the same mounting footprint on the CyberCat board and
cannot be used simultaneously.
P7
C NC NO
Alarm
P11
P10
P9
P8
P6
P2
C NC NO
Supervisory
C NC NO
Trouble
L
IN
E
2
S
Y
S
T
R
B
L
H
EAR
TBE
A
T
L
IN
E
1
OPTIONAL
DACT
OPTIONAL
CRM4 RELAY
OR
REVERSE
POLARITY
MODULE
OPTIONAL CRM4 RELAY,
NETWORK MODULES (RS485
& FIBER), OR REVERSE
POLARITY MODULE
OPTIONAL
SUPPLEMENTAL
POWER SUPPLY
OPTIONAL
SUPPLEMENTAL
LOOP MODULE
Exhibit 4-8: Mounting Locations for Optional Modules