3.0 SYSTEM COMPONENTS
3-36
CyberCat 254/1016 Installation Manual
UL S2203
Rev 14, 09/2015
P/N: 06-326
FM
3.10.6 SUPERVISED CONTROL MODULE, P/N 55-042
SUPERVISED CONTROL MODULE WITH ISOLATOR,
P/N 55-047
The Supervised Control Module (See Exhibit 3-72) is used to switch
an external power supply or audio amplifier to notification appliances.
The module monitors the external power input for loss of power and
signals the CyberCat panel accordingly. The module includes a tri-
color LED for instant indication of device status. The module is
capable of providing an optional pulsing output to signal different
states, when interfaced with the CyberCat addressable loop. The
isolator version provides complete short circuit isolation for NFPA
Class X wiring. A module cover plate (not shown) is included with
the module.
In addition to interfacing with notification appliances, the SCM can
also be used to operate either of the following interfaces:
3.10.6.1 SOLENOID PROTECTION ASSEMBLY, P/N 10-2360
The SCM can be connected to a single sprinkler solenoid rated up to
2 amps maximum at 24VDC. The Solenoid Protection Assembly
(See Exhibit 3-73)
must
be used when connecting a solenoid to the
SCM. Refer to Fike document 06-186 for compatible sprinkler
solenoids (Factory Mutual Approved Groups A-G).
Refer to Fike document 06-344, for more information.
3.10.6.2 MASTER-BOX INTERFACE, P/N 10-2413
The Master-box Interface (See Exhibit 3-74) provides the CyberCat
control panel with the ability to activate a Local Energy Type
Auxiliary Fire Alarm System (as noted by NFPA 72). The Master-box
Interface
must
be used in conjunction with a Supervised Control
Module (P/N 55-042).
Refer to Fike document 06-229, for more information.
Exhibit 3-72: Supervised
Control Module
Exhibit 3-73: Solenoid
Protection Assembly
Exhibit 3-74: Master-box
I
f