CIE-A-200 Control Panel Engineering and Commissioning Manual
62
Control Panel Fuses and Protection
Single Loop Addressable Panel
Loop output
1.2A current limiter
Monitored Outputs 1 and 2
750mA trip polyfuse
Auxiliary 24V DC supply
T500mA Time Delayed 20mm Glass
Mains
T4A Time Delayed 20mm Ceramic (in mains terminal block)
Battery Charger
1.2A current limiter
Battery (reverse polarity)
F3.15A Fast Blow 20mm (in line with battery leads) Glass
Note: Refer to the relevant sections in the manual for full details of input and output ratings.
Resistor Colour Codes
On colour coded resistors the band at one end will be spaced further apart than the others. The resistor
should be viewed with this band to the right as follows, reading from the left and side of the resistor:
Battery Calculations
Note:
An Excel spreadsheet (document no. 26-1765) is available to automatically work out both standby
battery calculations and loop loading calculations based on the quantities entered. This includes
ratings for legacy devices.
Current draw ratings for the control panel are as follows:
Band
4 Band
Codes
5 Band
Codes
1
1
st
Digit
1
st
Digit
2
2
nd
Digit
2
nd
Digit
3
Multiplier
3
rd
Digit
4
Tolerance
Multiplier
5
-
Tolerance
Colour
Digit
Multiplier
Black
0
1
Brown
1
10
Red
2
100
Orange
3
1,000
Yellow
4
10,000
Green
5
100,000
Blue
6
1,000,000
Violet
7
-
Grey
8
-
White
9
-
Gold
-
0.1
Silver
-
0.001
PRODUCT DESCRIPTION
QUANTITY
CURRENT DRAWN (mA)
TOTAL (mA)
Dev
DLUs
Product Code
Description
IS
IA
IS
IA
520-0001
Single Loop Control Panel
0
44.600
82.3
0.000
0.000
Back Light
0
1.000
1.000
0.000
0.000
Output 1 (MO1) (MAX 500mA depending on external load) IF USED
0
500.000
500.000
0.000
0.000
Output 2 (MO2) (MAX 500mA depending on external load) IF USED
0
500.000
500.000
0.000
0.000
Aux 24VDC (MAX 450mA depending on external load) IF USED
0
450.000
500.000
0.000
0.000