CIE-A-200 Control Panel Engineering and Commissioning Manual
19
Monitored Outputs (MON_OUT_1 & 2)
Outputs 1 and 2 are monitored circuits which are monitored for open and short circuit faults with a 10k EOL
resistor. Sounders used on monitored outputs must be 24v conventional type sounders.
Any relays must be dioded for polarisation and suppression.
Diodes are usually incorporated in fire
relays but if they are not incorporated use diodes part number 1N4002.
The diagram below shows the diode arrangement required if non-dioded relays are used on monitored
outputs.
The default setting for monitored output 1 is a
Monitored Sounder Output
and the default setting for
monitored output 2 is a
Common Fire Output
.
The maximum continuous output current for each output is
500mA.
Monitored Outputs can be set as follows:
Not Configured
Fire Output
Sounder Output
Sounder Output Cadence
Common Fault
Terminal
Description
+
Monitored Output positive connection
-
Monitored Output 0V connection
SCRN
Field cable screen connection