CIE-A-200 Control Panel Engineering and Commissioning Manual
32
Access Levels and Codes
The menu system is divided into four access levels in order to restrict access to those who require it. For
simple indication the status of the
Controls Enabled
light will show the level selected as follows:
Access Level
Description
Shift LED
Key Operation
Default Code
Page
0
– NORM
Normal
OFF
NO
N/A
32
1
– USER
User
ON
YES
8737
33
2
– SUPR
Supervisor
SLOW FLASH
NO
7877
34
3
– ENGR
Engineer
FAST FLASH
NO
3647
40
Access to the menu system requires either the operation of the
enable controls key
for access to Access
Level 1 (User)
,
or the correct entry of the relevant code for access to all other levels, in order to protect against
unauthorised access to the system. The codes may be changed using the CIE-A-200 OSP software or from
the Engineers menu on the panel.
A valid access level code must be entered in order access any of the menus.
Access Level 0 (Normal): Controls Enabled LED off
At Access Level 1 (Normal), the main
Fire Alarm Controls
are disabled and the Controls Enabled LED is
switched off.
A valid access level code must be entered or the key switch must be used in order access any of the menus.
Delay Override
To comply with EN54-2 Clause 7.11.1d, a manual call point (MCP) should be located next to the CIE
to override the delayed output by a manual operation.