CIE-A-200 Control Panel Engineering and Commissioning Manual
37
5. Enable / Disable
▼
Inputs
→
Detection Zone
This function allows the disablement or enablement of a detection-zone. Thus, all the input devices
(Manual Call Points, detectors and inputs) within that detection-zone will be disabled. The control
panel will indicate that disablements are present, a disablement event will be recorded in the log, the
device LED will still operate when activated and an event will be recorded in the log, but no
programmed actions will occur. The sounder within the device will still operate if triggered from
elsewhere on the system.
Inputs
→
Device
This function allows the disablement or enablement of an individual device. The control panel will
indicate that disablements are present, a disablement event will be recorded in the log, the device
LED will still operate when activated and an event will be recorded in the log, but no programmed
actions will occur. The sounder within the device will still operate if triggered from elsewhere on the
system.
Inputs
→
All Detection Zone
This function allows the disablement or enablement of all detection-zones. Thus, all the input devices
(Manual Call Points, detectors and inputs) will be disabled. The control panel will indicate that
disablements are present, a disablement event will be recorded in the log, the device LED will still
operate when activated and an event will be recorded in the log, but no programmed actions will
occur. The sounder within the device will still operate if triggered from elsewhere on the system.
Inputs
→
All Devices
This function allows the disablement or enablement of all devices. Thus, all the input devices (Manual
Call Points, detectors and inputs) will be disabled. The control panel will indicate that disablements
are present, a disablement event will be recorded in the log, the device LED will still operate when
activated and an event will be recorded in the log, but no programmed actions will occur. The sounder
within the device will still operate if triggered from elsewhere on the system.
Outputs
→
Sounders
This function allows the global disablement or enablement of all the sounders on the system. The
control panel will indicate that disablements are present and a disablement event will be recorded in
the log.
Outputs
→
Fire Outputs
This function allows the global disablement or enablement of all fire outputs on the system. The
control panel will indicate that disablements are present and a disablement event will be recorded in
the log.
Outputs
→
Fault Outputs
This function allows the global disablement or enablement of all fault outputs on the system. The
control panel will indicate that disablements are present and a disablement event will be recorded in
the log.
Group Disablement
This function allows the disablement or enablement of the group. The group is fixed and will disable
all Sounders, Fire outputs & Fault outputs. The control panel will indicate that disablements are
present and a disablement event will be recorded in the log.