CIE-A-200 Control Panel Engineering and Commissioning Manual
43
Panel I/O
→
Monitored Input Settings
This will allow the engineer to view or change the operation of the Monitored I/P settings.
Monitored Inputs can be programmed as follows.
FIRE EVENT
– I/P activation will mimic that of a remote fire input.
This can be set as:
Full Fire, Latching
Full Fire, Non-Latching
CONTROL EVENT
– I/P activation will mimic that of a panel control. The following
controls can be set:
Silence Alarms
Reset System
Sound Alarms
Silence Buzzer
TECHNICAL EVENT
– I/P activation will sound alarms but not put the panel into a
fire condition. This can be set as:
Latching
Non-Latching
CLASS CHANGE EVENT
– I/P activation will sound alarms only
This can be set as:
Latching
Non-Latching
Panel I/O
→
Aux Power Settings
This will allow the engineer to switch on or off the Aux power output.
This can be set as:
Off
On
Resettable - Reset System will cause the Aux
Power to reset
12. Panel Details
▼
Panel Details
→
Set access Codes
This will allow the engineer to change the access codes for access to the user menus.
The default codes are:
Access Level
Description
Default Code
0
– NORM
Normal
N/A
1
– USER
User
8737
2
– SUPR
Supervisor
7877
3
– ENGR
Engineer
3647
Panel Details
→
Software Version
This active control will allow the engineer to view the version of panel operating software implemented.
Panel Details
→
Enable Key Press Buzzer
Turns the buzzer on/off when a key is pressed.