CIE-A-200 Control Panel Engineering and Commissioning Manual
29
LED Indication
The operation of the LED indications on the front of the control panel is described below.
Description
Colour
State
Reason
1.
POWER
Green
Continuous
This indicates that power is being supplied to the
control panel from either the 230V AC mains supply,
or the standby batteries.
2.
TEST
Yellow
Continuous
This indicates that a test routine is in place. End all
tests to clear.
3.
DELAY
Yellow
Continuous
An action has been started which utilises a
programmed delay.
4.
FAULT
Yellow
Continuous
The control panel is in the fault state. Other
indicators will show the origin.
5.
SYSTEM FAULT
Yellow
Continuous
The system Fault LED indicates the presence of a
processor or a checksum error. Power the system
down to clear, reprogram all settings and test the
system.
6.
POWER FAULT
Yellow
Continuous
The mains supply or standby battery supply has
failed (check the fuses, battery and the 230V AC
supply.
7.
SOUNDER FAULT
Yellow
Continuous
A fault condition is present on a monitored sounder
circuit or on the addressable device loop sounders.
8.
DISABLED
Yellow
Continuous
This indicates that a disablement action is in place.
Enable all devices / actions to clear.
9.
SOUNDER DISABLED
Yellow
Continuous
This indicates that a sounder disablement action is in
place. Enable all devices / actions to clear.
10.
FIRE OUTPUT FAULT
Yellow
Continuous
A fault condition is present on a monitored Fire
Output circuit or on the addressable device loop
outputs.
11.
FIRE OUTPUT DISABLED
Yellow
Continuous
This indicates that a Fire Output disablement action
is in place. Enable all Fire Outputs to clear.
12.
FAULT OUTPUT DISABLED
Yellow
Continuous
This indicates that a Fault Output disablement action
is in place. Enable all fault outputs to clear.
13.
ALARM CONFIRMATION
Yellow
Continuous
A smoke detector is in the alarm confirmation state,
awaiting confirmation or reset.
14.
FIRE
Red
Continuous
The control panel is in the fire state. Other indicators
will show the origin.
15.
ZONE 1-32
Red
Continuous
The control panel is in the fire state. The zone LED
will illuminate to indicate the zone where the fire as
occurred.
More zone LEDs may be illuminated if fires have
been detected in more than one zone.