CIE-A-200 Control Panel Engineering and Commissioning Manual
38
6. Set Time & Date
▼
Set Time & Date.
This allows the time and date to be adjusted.
DST Settings.
This allows the Daylight Saving Time to be adjusted.
7. Find Device
This function allows the user to switch on the LED and sounder (if they are present) at any device on
the loop in order to aid in locating its position. It cannot be used to turn on the LED of I/O Modules,
since this would also turn on the output which would not usually be desirable.
Up, Down and Esc options allow the adjacent devices to be located, and the test to be ended.
8. Diagnostics
There are four types of diagnostics on the Single Loop Panel, a Loop diagnostics, a PSU diagnostics, an
LED diagnostics & Peripheral Bus diagnostics. All four come out of the User USB port on the back board.
The LED diagnostics will send the CIE LED status to the PC based diagnostic software.
▼
Diagnostics
→
Loop Diagnostics
This turns the loop diagnostics on or off. This must be set to on for the PC based diagnostic software to
get data from the loop.
Diagnostics
→
LED Diagnostics
This turns the LED diagnostics on or off. This must be set to on for the CIE LED status data to be sent to
the PC based diagnostic software.
Diagnostics
→
PSU Diagnostics
This turns the PSU diagnostics on or off. This must be set to on for the PC based diagnostic software to
get data from the PSU.
The PSU Information screen will display PSU status on the Panel screen. The following information will
be displayed:
Charger State
Normal
Charger Fault
Battery Internal Resistance Fault
PCB Temperature
Normal
Low Temperature
High Temperature
Battery Supply
Normal
Low Voltage
Lowest Voltage
Over Voltage
Battery Temperature
Normal
Low Temperature
High Temperature