CIE-A-200 Control Panel Engineering and Commissioning Manual
44
13. Peripheral Bus
▼
Peripheral Bus
→
Sync Event Logs
This will allow the engineer to sync the event logs of the main panel to the RDUs.
14. Auto Zoning
▼
Auto Zoning
→
Start Auto Zoning
This will allow the engineer to change the zone of loop devices by triggering an alarm. On clearing the
alarm the device that entered the alarm condition will take on the newly assigned zone.
Auto Zoning
→
Stop Auto Zoning
This will allow the engineer to end the Auto Zoning mode.
15. Alarm Re-sound
▼
This function allows the sounders to either re-sound on another alarm or to remain in the silenced
mode.