HIGH LEVEL INTERFACE
42
P/N 06-158
UL S3217
Rev 5, 02/2015
FM 3020297
MINOR FLT CLR: VZnnn
The VESDA detector, Zone nnn,
which previously reported MINOR
FAULT has cleared.
This is an expected event if the
VESDA fault is cleared. Note
events if desired.
NETWORK FAULT: VZ nnn
The VESDAnet has reported a fault
on the VESDA detector
programmed for Zone nnn.
Locate VESDA programmed for
Zone nnn. Use Vision System
software or Programmer to
diagnose VESDAnet fault.
NETWORK F CLR: VZ nnn
The previously reported NETWORK
FAULT on the VESDA detector
programmed for Zone nnn has
cleared.
This is an expected response when
the trouble clears. Make note of the
event, if necessary or problem
persists.
POWER FAULT: VZ nnn
The VESDA programmed for Zone
nnn is reporting a power fault.
Locate VESDA Zone nnn and check
the power connections.
POWER FLT CLR: VZ nnn
The VESDA detector, Zone nnn,
which previously reported POWER
FAULT, has power restored to
normal.
This is an expected event if the
power is restored to the VESDA
detector. Note event if desired.
SECTOR ACTION Vnnn-x
The VESDA detector’s sector x on
Zone nnn has reached the ACTION
level.
Locate VESDA nnn determine area
for sector x. Look for obvious signs
of obscuration/smoke.
SECTOR ALERT CLEAR
The VESDA detector that previously
reported a SECTOR ALERT event
has cleared below the ALERT level.
This is an expected event if the
obscuration falls below the ALERT
setting. Note event if desired.
SECTOR ALERT Vnnn-x
The VESDA detector’s sector x on
Zone nnn has reached the ALERT
level.
Locate VESDA nnn determine area
for sector x. Look for obvious signs
of obscuration/smoke.
SECTOR FIRE-1 CLEAR
The VESDA detector that previously
reported a FIRE-1 event has cleared
below the FIRE-1 level.
This is an expected event if the
obscuration falls below the FIRE-1
setting. Note event if desired.
SECTOR FIRE-1 Vnnn-x
The VESDA detector’s sector x on
Zone nnn has reached the FIRE-1
level.
Locate VESDA nnn determine area
for sector x. Look for obvious signs
of obscuration/smoke.
SECTOR FIRE-2 CLEAR
The VESDA detector that previously
reported a FIRE-2 event has cleared
below the FIRE-2 level.
This is an expected event if the
obscuration falls below the FIRE-2
setting. Note event if desired.
SECTOR FIRE-2 Vnnn-x
The VESDA detector’s sector x on
Zone nnn has reached the FIRE-2
level.
Locate VESDA nnn determine area
for sector x. Look for obvious signs
of obscuration/smoke.