HIGH LEVEL INTERFACE
30
P/N 06-158
UL S3217
Rev 5, 02/2015
FM 3020297
When the FIRE-2 LEVEL event is active and being viewed as in Exhibit 33, by pressing the F1 key on the
panel, the level details of the VESDA will be shown on this screen:
F I R E - 2
L E V E L :
V Z 0 0 1
C U R R E N T : 0 . 0 0 1 5 % / F T
0 2 : 1 5 : 1 9 P
1 1 / 1 5 / 2 0 0 5
E V E N T
0 0 1 0
O F
0 0 1 0
Exhibit 34: CyberCat/Cheetah Xi – FIRE-2 Level
Line 1 VESDA FIRE-2 level activated / Unit #
Line 2 Current live obscuration level being sent from detector. This unit will update as obscuration
changes at the VESDA
Line 3 Time and date stamp for this event
Line 4 Event number and total events on panel