HIGH LEVEL INTERFACE
32
P/N 06-158
UL S3217
Rev 5, 02/2015
FM 3020297
6.1.2 EVENT HISTORY MESSAGES
Should either cable connected to the HLI become disconnected, the following history message appears:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
V E S D A C O M M U N E R R O R
B
B O A R D L E V E L E V E N T
C
0 4 : 1 7 : 2 6 P M 1 2 / 3 0 / 9 7
D
E V T 0 0 2 / 0 0 2 C U R
Exhibit 37: Cheetah – Event Trouble
A1-20: Event message.
B1-20: Custom message for a board level event.
C1-20: Time and date stamp for this event.
D5-7: Event number in event history list.
D9-11: Total number of history events.
D12-14: ‘CUR’ = Current event history list. ‘HIS’ = Complete event history list (600 Total).
The following message appears when the trouble event clears is:
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
A
V E S D A C O M M U N R E S T O R E
B
B O A R D L E V E L E V E N T
C
0 4 : 1 7 : 2 6 P M 1 2 / 3 0 / 9 7
D
E V T 0 0 3 / 0 0 3 C U R
Exhibit 38: Cheetah – Event Restored
LCD lines B, C, and D are of the same format as for Exhibit 9-2 above.
6.2
CYBERCAT/CHEETAH XI VESDA LINK
If the serial cable between the CyberCat or Cheetah Xi and the HLI becomes disconnected, a trouble event is
recorded within 30 seconds. A re-connect of the HLI-to-Cheetah results in a trouble clear event. Only the
trouble relay of the main board and any programmed for Zone 254 are affected. None of the zones assigned
to VESDA devices are affected.
6.2.1 EVENT/HISTORY
MESSAGES
V E S D A M I S S I N G :
V Z 0 0 1
C U S T O M M S G
P A N E L
0 0 1
0 8 : 4 3 : 5 7 A
1 1 / 1 5 / 2 0 0 5
E V E N T
0 0 1 2
O F
0 0 1 2
Exhibit 39: CyberCat/Cheetah Xi– Event Trouble
Line 1 VESDA Detector communication has been lost at panel
Line 2 Custom Message of panel HLI is connected to.
Line 3 Time and date stamp for this event
Line 4 Event number and total events on panel