HIGH LEVEL INTERFACE
UL S3217
P/N 06-158
23
FM 3020297
Rev 5, 02/2015
♦
Action Level
= Supervisory and Trouble LEDs illuminate on Panel and piezo sounds supervisory pattern
(warble) and Supervisory State entered for the configured panel zone. The onboard Supervisory Relay
will energize and change states. On the CyberCat / Cheetah Xi this state is not latching and panel will
clear after obscuration drops below the
Fire 1
level. (Unless VESDA is set to latching on Alarms)
♦
Fire-2 Level
= Supervisory and Trouble LEDs illuminate on Panel, piezo sounds supervisory pattern
(warble) and Supervisory State activated for the configured panel zone. (This is a new smoke level but
audibles will NOT resound if they were silenced in
Fire 1
Level). The onboard Supervisory Relay will
remain energized as it was in
Fire 1
Level. On the CyberCat / Cheetah Xi this state is not latching and
panel will clear after obscuration drops below the
Fire 2
level. (Unless VESDA is set to latching on
Alarms)
L
Note:
Pre-Alarm conditions are non-latching in the control panel. However, if the VESDA is configured to
latch on alarm states, the VESDA will keep that level from clearing on the control panel.
5.6.3 TROUBLE
OPERATION
If a VESDA is configured in the Cheetah Xi or CyberCat control panel for
TROUBLE
, the following levels and
states will be seen and activated on the panel:
♦
Alert Level
= Trouble LED illuminates on Panel and piezo sounds trouble pattern (constant). No onboard
relay transfers during this state. This condition is non-latching and will clear when the obscuration level
drops below the
Alert
Level in the VESDA. (Unless VESDA is set to latching on Alarms)
♦
Action Level
= Trouble LED illuminates on Panel and piezo sounds trouble pattern (constant). No
onboard relay transfers during this state. This condition is non-latching and will clear when the
obscuration level drops below the
Action
Level in the VESDA. (Unless VESDA is set to latching on
Alarms)
L
Note:
If panel has been silenced during the
Alert
Level, the panel LED and Piezo do NOT resound
when Action Level is reached.
♦
Fire-1 Level
= Trouble LED illuminates on Panel and piezo sounds trouble pattern (constant). The
onboard Trouble Relay will transfer at this point. On the CyberCat / Cheetah Xi this state is not latching
and panel will clear after obscuration drops below the
Fire 1
level. (Unless VESDA is set to latching on
Alarms)
♦
Fire-2 Level
= Trouble LED illuminates on Panel and piezo sounds trouble pattern (constant), and
Trouble State activated for the configured panel zone. (This is a new smoke level but audibles will NOT
resound if they were silenced in
Fire 1
Level). The onboard Trouble Relay will transfer at this point. On
the CyberCat / Cheetah Xi this state is not latching and will clear when the obscuration level drops below
the
Fire 2
level. (Unless VESDA is set to latching on Alarms)
L
Note:
If panel has been silenced during the
Fire 1
Level, the panel LED and Piezo do NOT resound when
Fire 2
Level is reached.
L
Note:
Pre-Alarm conditions are non-latching in the control panel. However, if the VESDA is configured to
latch on alarm states, the VESDA will keep that level from clearing on the control panel.