HIGH LEVEL INTERFACE
36
P/N 06-158
UL S3217
Rev 5, 02/2015
FM 3020297
7.2
CHEETAH XI / CYBERCAT
7.2.1 F6 - DIAGNOSTIC MENU #2
D I A G N O S T I C M E N U 2
F 1 - F 4 - V E S D A 1
F 2 - F 5 - V E S D A 2
F 3 - F 6 -
Exhibit 46: Diagnostic Menu 2
7.2.2 F4 - VESDA 1
V E S D A Z O N E N U M : 0 0 1
>
C U R R E N T : 0 . 0 0 0 0 % / F T
A L : - . - - - - A C : - . - - - -
F 1 : - . - - - - F 2 : - . - - - -
Exhibit 47: VESDA Diagnostics Menu
7.2.3 F5 - VESDA 2
V E S D A Z O N E
N U M :
0 0 1
>
E N T E R
F O R
F A U L T
L I S T
- - - - - -
- - -
- - -
- - -
- - - - - -
- - -
- - -
- - -
Exhibit 48: VESDA Diagnostics Menu
Line 1
VESDA zone number for diagnosis. Position cursor in ones, tens, or hundreds field
for zone number. Press + or – to change value at cursor.
Arrow/carrot at far right moves back and forth to display communication is active
between panel and VESDA.
Line 2
Press enter to list the VESDA status for the VESDA zone number displayed in line 1.
L
Note:
For complete list of possible messages that could display on CyberCat or Cheetah Xi screen, as
well as possible causes and solutions, refer to Appendix 2 (Event Messages) of this manual, and the
CyberCat or Cheetah Xi Product Manual
Line 1
VESDA zone number for diagnosis. Position cursor in ones, tens, or hundreds field for zone
number. Press + or – to change value at cursor.
Arrow/carrot at far right moves back and forth to display active communication between
panel and VESDA. If not toggling, then VESDA is not communicating with Control Panel.
Line 2
Displays current obscuration being seen at the detector (for zone number in top line). This
updates upon each press of ENTER button (noted in %/ft value)
Line 3
AL
arm setting for Detector located in the zone displayed in line 1.
AC
tion setting for Detector located in the zone displayed in line 1.
Line 4
F1
, Fire 1 setting for Detector located in the zone displayed in line 1.
F2
, Fire 2 setting for Detector located in the zone displayed in line 1.